199
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
ALLM
SPT lo alert limit/occ
-10-245
dF
SPLO
60
SPT hi alert limit/occ
-10-245
dF
SPHO
85
SPT lo alert limit/unocc
-10-245
dF
SPLU
45
SPT hi alert limit/unocc
-10-245
dF
SPHU
100
EDT lo alert limit/occ
-40-245
dF
SALO
40
EDT hi alert limit/occ
-40-245
dF
SAHO
100
EDT lo alert limit/unocc
-40-245
dF
SALU
40
EDT hi alert limit/unocc
-40-245
dF
SAHU
100
RAT lo alert limit/occ
-40-245
dF
RALO
60
RAT hi alert limit/occ
-40-245
dF
RAHO
90
RAT lo alert limit/unocc
-40-245
dF
RALU
40
RAT hi alert limit/unocc
-40-245
dF
RAHU
100
OAT lo alert limit
-40-245
dF
OATL
-40
OAT hi alert limit
-40-245
dF
OATH
150
RARH low alert limit
0-100
%
RRHL
0
RARH high alert limit
0-100
%
RRHH
100
OARH low alert limit
0-100
%
ORHL
0
OARH high alert limit
0-100
%
ORHH
100
SP low alert limit
0-5
" H2O
SPL
0
SP high alert limit
0-5
" H2O
SPH
2
BP lo alert limit
-0.25-0.25
" H2O
BPL
-0.25
BP high alert limit
-0.25-0.25
" H2O
BPH
0.25
IAQ high alert limit
0-5000
IAQH
1200
BP__
Building Press. Config
0-5
BLDG_CFG
0
Building Pressure Sensor
Enable/Disable
BPSENS
Disable
Bldg. Press. (+/-) Range
0.10 to 0.25
" H2O
BP_RANGE
0.25
Building Pressure Setp.
-0.25 to 0.25
" H2O
BPSP
0.05
BP Setpoint Offset
0 to 0.5
^" H2O
BPSO
0.05
Power Exhaust On Setp.1
0 to 100
%
PES1
25
Power Exhaust On Setp.2
0 to 100
%
PES2
75
VFD/Act. Fire Speed/Pos.
0 to 100
%
BLDGPFSO
100
VFD/Act. Min. Speed/Pos.
0 to 100
%
BLDGPMIN
10
VFD Maximum Speed
0 to 100
%
BLDGPMAX
100
BP 1 Actuator Max Pos.
85 to 100
%
BP1SETMX
100
BP 2 Actuator Max Pos.
85 to 100
%
BP2SETMX
100
BP Hi Cap VFD Clamp Val.
5 to 25
%
BLDGCLMP
10
Fan Track Learn Enable
Yes/No
DCFM_CFG
NO
Fan Track Learn Rate
5-60
min
DCFMRATE
15
Fan Track Initial DCFM
-20000 to 20000
CFM
DCFMSTRT
2000
Fan Track Max Clamp
0 to 20000
CFM
DCFM_MAX
4000
Fan Track Max Correction
0 -20000
CFM
DCFM_ADJ
1000
Fan Track Internl EEPROM
-20000 to 20000
CFM
DCFM_OFF
0
Fan Track Internal RAM
-20000 to 20000
CFM
DCFM_RAM
0
Fan Track Reset Internal
Yes/No
DCFMRSET
No
Supply Air CFM Config
1 to 2 (multi-text strings)
SCFM_CFG
1
Bldg.Pres.PID Run Rate
5 to 120
sec
BPIDRATE
10
Bldg.Press. Prop. Gain
0 to 5
BLDGP_PG
1
Bldg.Press. Integ. Gain
0 to 2
BLDGP_IG
1
Bldg.Press. Deriv. Gain
0 to 5
BLDGP_DG
0.5
BP 1 Serial Number 1
0 to 9999
BP_1_SN1
0
BP 1 Serial Number 2
0 to 6
BP_1_SN2
0
BP 1 Serial Number 3
0 to 9999
BP_1_SN3
0
BP 1 Serial Number 4
0 to 254
BP_1_SN4
0
BP1 Cntrl Angle Lo Limit
0-90
BP1_CALM
35
BP 2 Serial Number 1
0 to 9999
BP_2_SN1
0
BP 2 Serial Number 2
0 to 6
BP_2_SN2
0
BP 2 Serial Number 3
0 to 9999
BP_2_SN3
0
BP 2 Serial Number 4
0 to 254
BP_2_SN4
0
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...