200
BP__ (cont)
BP2 Cntrl Angle Lo Limit
0-90
BP2_CALM
35
COOL
Enable Compressor A1
Enable/Disable
CMPA1ENA
Enable
Enable Compressor A2
Enable/Disable
CMPA2ENA
Enable
Enable Compressor A3
Enable/Disable
CMPA3ENA
Enable
Enable Compressor B1
Enable/Disable
CMPB1ENA
Enable
Enable Compressor B2
Enable/Disable
CMPB2ENA
Enable
Enable Compressor B3
Enable/Disable
CMPB3ENA
Enable
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
Enable
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
Enable
CSB A3 Feedback Alarm
Enable/Disable
CSB_A3EN
Enable
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
Enable
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
Enable
CSB B3 Feedback Alarm
Enable/Disable
CSB_B3EN
Enable
Capacity Threshold Adjst
-10 to 10
Z_GAIN
1
Compressor Lockout Temp
-25 to 55
dF
OATLCOMP
40
Lead/Lag Configuration
LEAD_LAG
Motor Master Control ?
Yes/No
MOTRMAST
No
Maximum Condenser Temp
dF
SCT_MAX
Minimum Condenser Temp
dF
SCT_MIN
A1 is a Digital Scroll
Yes/No
DIGCMPA1
A1 Min Digital Capacity
%
MINCAPA1
Dig Scroll Adjust Delta
%
DSADJPCT
Dig Scroll Adjust Delay
sec
DSADJDLY
Dig Scroll Reduce Delta
%
DSREDPCT
Dig Scroll Reduce Delay
sec
DSREDDLY
Dig Scroll Reduction OAT
dF
DSREDOAT
Dig Scroll Max Only OAT
dF
DSMAXOAT
Min Load Valve Enable
Enable/Disable
MLV_ENAB
Hi SST Alert Delay Time
5 to 30
min
HSSTTIME
10
Rev Rotation Verified ?
Yes/No
REVR_VER
Use CSBs for HPS Detect
Yes/No
CSBHPDET
DEHU
Dehumidification Config
0-3
DHSELECT
0
Dehumidification Sensor
1-3
DHSENSOR
1
Econ disable in DH mode?
Yes/No
DHECONEN
No
Vent Reheat Setpt Select
0-1
DHVHTCFG
0
Vent Reheat RAT offset
0-8
^F
DHVRAOFF
0
Vent Reheat Setpoint
55-95
dF
DHVHT_SP
70
Dehumidify Cool Setpoint
40-55
dF
DHCOOLSP
45
Dehumidify RH Setpoint
10-90
%
DHRELHSP
55
Humidimizer Adjust Rate
secs
HMZRRATE
Humidimizer Prop. Gain
HMZR_PG
Bypass EXV Max Open
%
BYP_MAX
Condenser EXV Max Open
%
COND_MAX
LAT Sample Buffer Length
LAT_SAMP
LAT Sample Rate seconds
secs
LAT_RATE
DISP
Metric Display
Off/On
DISPUNIT
Off
Language Selection
0-1
LANGUAGE
0
Password Enable
Enable/Disable
PASS_EBL
Enable
Service Password
0000-9999
PASSWORD
1111
Contrast Adjustment
0-255
CNTR_ADJ
0
Brightness Adjustment
0-255
BRTS_ADJ
0
DLVT
Dmd Level Lo Heat On
-1 to 2
^F
DMDLHON
1.5
Dmd Level(+) Hi Heat On
0.5 to 20.0
^F
DMDHHON
0.5
Dmd Level(-) Lo Heat Off
0.5 to 2.0
^F
DMDLHOFF
1
Dmd Level Lo Cool On
-1 to 2
^F
DMDLCON
1.5
Dmd Level(+) Hi Cool On
0.5 to 20.0
^F
DMDHCON
0.5
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...