Fig. 77 — Charging Chart — 48/50P070 Standard Units — Circuit A
Fig. 78 — Charging Chart — 48/50P070 Standard Units — Circuit B
70 Ton STD CAP CIRCUIT A Charging Chart
All Compressors on a Circuit Must be Operating
All Outdoor Fans Must be Operating
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
55
60
65
70
75
80
85
90
95
100
105
110
115
120
Outdoor Air Temperature (deg F)
Saturated Discharge Temperature (deg F)
Reduce Charge if Above Curve
Add Charge if Below Curve
SST= 45 F
SST= 60 F
SST= 30 F
70 Ton STD CAP CIRCUIT B Charging Chart
All Compressors on a Circuit Must be Operating
All Outdoor Fans Must be Operating
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
55
60
65
70
75
80
85
90
95
100
105
110
115
120
Outdoor Air Temperature (deg F)
Saturated Discharge Temperature (deg F)
Reduce Charge if Above Curve
Add Charge if Below Curve
SST= 45 F
SST= 60 F
SST= 30 F
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...