83
Cooling Percentage
R
Input Register
(Float)
9
clg_pct
AV
13
nvoClgPct
SNVT_count_inc(
9)
Network Status of Cool-
ing Demand in percent-
age (%)
Cooling Set point
R/W
Holding Regis-
ter (Float)
57
sat_stpt_cl
AV
66
Select
Network Parameter to
set the Cooling Set point
55 °F (Default)
CSAT_HI
R
Discrete Input
28
csat_hi
BV
80
Select
Network Parameter to
set CSAT HI
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Current Alarm
R
Input Register
(Float)
11
current_alarm
AV
17
nvoCurAl
m
SNVT_count_inc(
9)
Alarm Status of unit:
0 = No Alarm
1-7 = UPM1 Fault Code
9-16 =UPM2 Fault Code
20 = Output Overridden
via Keypad
30 = Sensor Failure
40 = Leaving Water
Temp Alarm
50 = Zone Temp Alarm
60 = Discharge Air Tem-
perature
70 = Filter Alarm/Com-
pressors 1 & 2 Runtime
90 = High CO
2
Level
Alarm
100 = Supply Fan
Locked
110 = Static Press Low
CWV Command
R
Discrete Input
29
cwv_com-
mand
BV
109
nvoCwvCo
mmand
SNVT_switch(95)
Condenser Water Valve
Command Status
0 = Off
1 = On
CWV_FAIL
R
Discrete Input
30
cwv_fail
BV
107
Select
Condenser Water Valve
Failure Alarm
CWV_HAND
R
Discrete Input
31
cwv_hand
BV
108
Select
Condenser Hand Alarm
Condenser Valve Com-
mand Enabled without
unit commanded
DA_SENS_FAIL
R
Discrete Input
32
da_sen
BV
31
Select
Network Alarm Indicat-
ing Discharge Air Sen-
sor Failure
0 = Normal
1 = Alarm
Damper Output
Cmd
R
Discrete Input
33
damper_cmd
BV
49
nvoDamp-
erCmd
SNVT_switch(95)
Damper Output Status
0 = Closed
1 = Open
DAT Sensor Selec-
tion
R/W
Holding Regis-
ter (Float)
15
dat_sel
AV
81
Select
Discharge Air Tempera-
ture Sensor Setup
0 = Hardwired Sensor
(Default)
1= BAS Supplied DAT
value
DAT Sensor Source
Selection Status
R
Input Register
(Float)
13
dat_sel_sta
AV
82
Select
Discharge Air Tempera-
ture Sensor Selection
Status
0 = Hardwired Sensor
DAT
1 = BAS Supplied DAT
DAT_HI
R
Discrete Input
34
dat_hi
BV
29
Select
Discharge Air Tempera-
ture Sensor Alarm (Cool-
ing)
0 = Normal
1 = High DAT (Default:
>70 °F)
Demand Level
R/W
Holding Regis-
ter (Float)
17
demand_level
AV
64
Select
Demand Level Set point
Adjust in °F
DO_LOCK
R
Discrete Input
35
do_lock
BV
37
Select
Network Parameter to
set DO LOCK
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
DPS Alarm
R
Discrete Input
36
DPS_alarm
BV
77
Select
Network Parameter to
set DPS Alarm
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
DX_RNTM
R
Discrete Input
37
dx_rntm
BV
79
Select
Network Parameter to
set DX RNTM
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Table 66 — Integration Points List (cont)
PROTOCOL MAP
MODBUS
BACNET
LONWORKS
OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME
SNVT
DESCRIPTION
Содержание Omnizone 50BVC