LEGEND
Table 11 — Electrical Data — with Belt Drive Motor (50BVC,Q)
MODELS
RATED
VOLTAGE
VOLTAGE
MIN/MAX
COMPRESSOR
INDOOR FAN MOTOR
POWER SUPPLY
QTY
RLA
(EACH)
LRA
(EACH)
MOTOR
HP
MOTOR
QTY
FLA
(EACH)
MIN
CIRCUIT
AMPS
MAX FUSE/
HACR
020
208-230/3/60
197/253
2
29.5
195.0
1.5
2
4.8
76.0
100
2
29.5
195.0
2.0
2
6.2
78.8
100
2
29.5
195.0
3.0
2
8.0
82.4
110
2
29.5
195.0
5.0
2
13.4
93.2
110
460/3/60
414/506
2
14.7
95.0
1.5
2
2.4
37.9
50
2
14.7
95.0
2.0
2
3.1
39.3
50
2
14.7
95.0
3.0
2
3.9
40.9
50
2
14.7
95.0
5.0
2
6.6
46.3
60
575/3/60
518/632
2
12.2
80.0
1.5
2
2.0
31.5
40
2
12.2
80.0
2.0
2
2.6
32.7
40
2
12.2
80.0
3.0
2
3.7
34.9
45
2
12.2
80.0
5.0
2
5.4
38.3
50
024
208-230/3/60
197/253
2
30.1
225.0
2.0
2
6.2
80.1
110
2
30.1
225.0
3.0
2
8.0
83.7
110
2
30.1
225.0
5.0
2
13.4
94.5
110
460/3/60
414/506
2
16.7
114.0
2.0
2
3.1
43.8
60
2
16.7
114.0
3.0
2
3.9
45.4
60
2
16.7
114.0
5.0
2
6.6
50.8
60
575/3/60
518/632
2
12.2
80.0
2.0
2
2.6
32.7
40
2
12.2
80.0
3.0
2
3.7
34.9
45
2
12.2
80.0
5.0
2
5.4
38.3
50
028
208-230/3/60
197/253
2
48.1
245.0
3.0
2
8.0
124.2
150
2
48.1
245.0
5.0
2
13.4
135.0
175
460/3/60
414/506
2
18.6
125.0
3.0
2
3.9
49.7
60
2
18.6
125.0
5.0
2
6.6
55.1
70
575/3/60
518/632
2
14.7
100.0
3.0
2
3.7
40.5
50
2
14.7
100.0
5.0
2
5.4
43.9
50
034
208-230/3/60
197/253
2
55.8
340.0
5.0
2
13.4
152.4
200
460/3/60
414/506
2
26.9
173.0
5.0
2
6.6
73.7
100
575/3/60
518/632
2
23.7
132.0
5.0
2
5.4
64.1
80
FLA
— Full Load Amps
HP
— Horsepower
LRA