64
TEMPERATURE SETPOINT
Access: Temperature screen, [
Stpt] softkey
The Temperature Setpoint (see Fig. 66) screen allows the user to
view effective cooling setpoint. Also, it allows the user to change
the supply air setpoint, differential setpoint and high temperature
alarm.
Fig. 66 — Temperature Setpoint Screen
Click the
[
PREV]
softkey to return to the Temperature screen
or click the
[
CMV]
softkey to access the Condenser Water
Valve screen. See Table 52 for screen function information.
CONDENSER WATER VALVE
Access: Temperature Setpoint screen, [
CMV] softkey
The Condenser Water Valve screen (see Fig. 67) allows the user to
view the condenser water valve status. It also allows the user to
change the condenser water valve delay time and to enable the
alarm for the condenser water valve.
Fig. 67 — Condenser Water Valve Screen
Click the
[
PREV]
softkey to return to the Temperature Setpoint
screen. See Table 53 for screen function information.
HEATING/COOLING (HEAT/COOL)
Access: Home Screen
The Heating/Cooling screen (see Fig. 68) allows the user to view
the current unit mode, cooling PID loop strength, and various
compressor information.
Fig. 68 — Heating/Cooling Screen
Click the
[
PREV]
softkey to return to the Home screen, click
the
[
Alarm]
softkey to access the Alarm screen or click the
[
Stpt]
softkey to access the Heating/Cooling Setpoint screen.
See Table 54 for screen function information.
Table 51 — Temperature Screen Functions
FIELD / KEY
FUNCTION / INFORMATION
Supply Air Temperature
(non-adjustable)
Displays the current Supply Air
Temperature
Outside Air Temperature
(non-adjustable)
Displays the current Outside Air
Temperature
Leaving Water Temperature
(non-adjustable)
Displays the current Leaving Water
Temperature
Entering Water
Temperature
(non-adjustable)
Displays the current Entering Water
Temperature
[
Prev]
Softkey access to previous screen
[
Stpt]
Softkey access to the Temperature
Setpoint screen
Table 52 — Temperature Setpoint Screen Functions
FIELD / KEY
FUNCTION / INFORMATION
Supply Air Set Point
(adjustable)
Displays the current Supply Air set point
Supply Air Stpt Diff
(adjustable)
Displays the current Supply Air set point
differential
Supply Air Temp High
Alarm
(adjustable)
Displays the current Supply Air high alarm
set point
Effective Cooling Setpoint
(non-adjustable)
Displays the current effective cooling
setpoint
Setpoint Adjustment
(adjustable)
Displays the current setpoint adjustment
Economizer Operation
Temp
(adjustable)
Displays the current setting at which the
Economizer will start to operate
[
Prev]
Softkey access to previous screen
[
CMV]
Softkey access to the Condenser Water
Valve screen
Table 53 — Condenser Water Valve Screen
Functions
FIELD / KEY
FUNCTION / INFORMATION
Condenser water vlv delay
(adjustable)
Displays the current condenser water valve
delay time
Condenser valve status
(non-adjustable)
Displays the current condenser water valve
status
Enable alarms for CWV
(adjustable)
Displays the current status for the alarming
of the condenser water valve
[
Prev]
Softkey access to previous screen