UNIT FAN
Access: Home Screen
The Unit Fan screen (see Fig. 50) allows the user to view all the
current values of the supply fan.
Fig. 50 — Unit Fan Screen
Click the
[
PREV]
softkey to return to the Home screen, click
the
[
Switch]
softkey to access the Supply Fan Lockout screen,
or click the
[
Stpt]
softkey to access the Fan Setpoints screen.
See Table 38 for screen function information.
UNIT OPERATION SETPOINT
Access: Unit Operation screen
[
Stpt] softkey)
The Unit Operation Setpoint screen (see Fig. 51) allows the user to
make configuration changes.
Fig. 51 — Unit Operation Setpoint Screen
Click the
[
PREV]
softkey to return to the Unit Operation
screen or click the
[
Archive]
softkey to access the Archive-
Commissioning screen. See Table 39 for screen function
information.
Table 38 — Unit Fan Screen Functions
FIELD / KEY
FUNCTION / INFORMATION
Supply fan S/S Command
(non-adjustable)
On - Fan is running
Supply Fan
(non-adjustable)
Supply fan capacity
Fan Start Counter (Total)
(non-adjustable)
Total number of fan starts
Fan Start Counter (Last hr)
(non-adjustable)
Total number of fan starts in the last hour
Runtime (Hours since
FILTR service)
(non-adjustable)
Total number of hours since the filters
were changed
Table 39 — Unit Operation Setpoint Screen
Functions
FIELD / KEY
FUNCTION / INFORMATION
Software enabled by
(adjustable)
Manual_On
Digital_Input
Keypad_Schedule
BAS_Command
Reset Sensor Location
(adjustable)
Outside Air
Return Air
Mixed Air
Number of Compressors
(adjustable)
1 Stage
2 Stages
3 Stages
4 Stages
Hardware Installed
(adjustable)
FLEX
: 6126 controller only
FLEX + EXPANDER
: 6126 controller
and 8160 expander module
Compressor Control
(adjustable)
Disch Air Control
Fan Operation
(adjustable)
S/S + VFD
Start/Stop
Return Fan
(adjustable)
Not Installed
Installed
Cool Options
(adjustable)
C HGRH
Cooling Only
CO2 Sensor Opt
(adjustable)
No CO2
CO2 Monitoring
CO2 Mon + Damper
BAS CO2 Monitoring
BAS CO2 Mon + Damper
Open when fan runs
Humidity Option
(adjustable)
DAC MOD
RH+DAC MOD
BAS MOD
Economizer Options
(adjustable)
Disabled
Economizer
Return Fan Overload
(adjustable)
Not Installed
Installed
Supply Fan Overload
(adjustable)
Not Installed
Installed
Return Duct Hi Static
(adjustable)
Not Installed
Installed
Supply Duct Hi Static
(adjustable)
Not Installed
Installed
Water DPS
(adjustable)
Not Installed
Installed