80
SENSORS AND INTEGRATION POINTS
Refer to Table 65 for factory-provided sensors and Table 66 for a
detailed integration points list.
Table 65 — Factory-Provided Sensors for VAV Units 50BVJ,W
*1 per compressor.
UNIT
DESCRIPTION
QTY
SHIPPING LOCATION
INSTALLATION LOCATION
50BVJ 020-034
Supply Air Temperature sensor
1
loose for field installation
Supply air stream
Return Air Temperature Sensor
1
loose for field installation
Return air stream
Entering Water Temperature
1
Installed
Condenser entering water
Leaving Water Temperature
1
Installed
Condenser leaving water
Duct Static Pressure Sensor
1
loose for field installation
Supply air stream
Compressor Current Transducer
*
Installed
Unit electrical box
50BVW 034-064
Supply Air Temperature Sensor
1
loose for field installation
Supply air stream
Return Air Temperature Sensor
4
loose for field installation
Return air stream
Entering Water Temperature
1
Installed
Condenser entering water
Leaving Water Temperature
1
Installed
Condenser leaving water
Duct Static Pressure Sensor
1
loose for field installation
Supply air stream
Compressor Current Transducer
*
Installed
Unit electrical box
Table 66 — Integration Points List
PROTOCOL MAP
MODBUS
BACNET
LONWORKS
OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME
SNVT
DESCRIPTION
Alarm Status
R
Discrete Input
5
alm_status
BV
24
nvoAlm-
Status
SNVT_switch(95)
Alarm Status of Unit (see
“Current Alarm” for more
information)
Allow CWV Alarm
R/W
Coil
1
allow_cwv_alr
m
BV
106
Select
Enable Condensate
Water Valve Alarm Pass
Through
0 = Off
1 = Enable CWV Alarm
BAS CO2 Sensor
Value
R/W
Holding Regis-
ter (Float)
1
bas_co2_val
AV
49
Select
CO
2
Sensor Value pro-
vided by BAS in PPM
BAS DAT Sensor
R/W
Holding Regis-
ter (Float)
3
bas_dat_val
AV
90
Select
Discharge Air Tempera-
ture (DAT) provided by
BAS in °F
BAS Return Air
Temp
R/W
Holding Regis-
ter (Float)
5
bas_rat
AV
29
Select
Return Air Temperature
Value provided by the
BAS
BAS RH Sensor
Value
R/W
Holding Regis-
ter (Float)
7
bas_rh_sen_
val
AV
56
Select
Relative Humidity (RH)
provided by BAS in %
BAS SD Input
R/W
Coil
2
bas_sd_in
BV
91
Select
Network Parameter to
set the BAS Smoke
Detector Alarm
Boilerless-Econo-
mizer Status
R
Input Register
(Float)
1
econ_boil_-
mode_stat
AV
34
Select
Economizer Option Status
0 = Disabled
1 = Water Side Econo-
mizer
BRN
R
Discrete Input
6
brn_2st
BV
10
Select
Network Alarm indicat-
ing Brownout sense on
UPM1
BRN
R
Discrete Input
7
brn_4st
BV
58
Select
Network Alarm indicat-
ing Brownout sense on
UPM2
BV Occupancy
Command (BAS)
R/W
Coil
3
occupan-
cy_cmd
BV
1
nviOc-
cBASCmd
SNVT_switch(95)
Network Parameter to
set the Occupancy Com-
mand
0 = Unoccupied (Default)
1 = Occupied
C1_FAIL
R
Discrete Input
8
comp1_fail
BV
150
Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed