84
Eff HGR Mod Valve
1
R
Input Register
(Float)
15
eff_hgr_-
mod_vlv1
AV
28
nvoEffHgr-
ModVlv1
SNVT_lev_per-
cent(81)
Hot Gas Reheat Modu-
lating Valve Output Sta-
tus in %
Eff RA Fan Speed
R
Input Register
(Float)
45
eff_ra_fan_-
speed
AV
162
nvoEffRa-
FanSpeed
SNVT_lev_per-
cent(81)
Supply Air Fan Speed
Network Status in %
Eff RA Static Pres-
sure
R
Input Register
(Float)
47
eff_ra_sta_-
press
AV
163
nvoEffRa-
StaPress
SNVT_count_inc(
9)
Network Status of the
Supply Duct Static Pres-
sure Sensor
Eff SA Fan Speed
R
Input Register
(Float)
17
eff_sa_fan_-
speed
AV
55
nvoEffSa-
FanSpeed
SNVT_lev_per-
cent(81)
Supply Air Fan Speed
Network Status in %
Eff SA Static Pres-
sure
R
Input Register
(Float)
19
eff_sa_sta_-
press
AV
53
nvoEffSa-
StaPress
SNVT_-
press_p(113)
Network Status of the
Supply Duct Static Pres-
sure Sensor
Eff Zone CO2 Lev
R
Input Register
(Float)
21
eff_zn_-
co2_lev
AV
25
nvoEffZn-
Co2Lev
SNVT_count_inc(
9)
Network Status of the
CO
2
Sensor Levels in
PPM
Effect EW Temp
R
Input Register
(Float)
23
eff_ewt
AV
62
nvoEffEwt
SNVT_-
temp_p(105)
Network Status of the
Entering Water Tem-
perature in °F
Effect Leaving Wtr
Temp
R
Input Register
(Float)
25
eff_lwt
AV
11
nvoEffLwt
SNVT_-
temp_p(105)
Network Status of the
Entering Water Tem-
perature in °F
Effect Outdoor Air
Temp
R
Input Register
(Float)
27
eff_rat
AV
75
nvoEffRat
SNVT_-
temp_p(105)
Network Status of the
Return Air Temperature
in °F
ELW_SENS_FAIL
R
Discrete Input
38
elw_sen
BV
72
Select
Network Parameter to
set ELW sensor FAIL
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Enabled Stages
R
Input Register
(Float)
29
enabled_cl-
stages
AV
68
Select
Network Status of the
number of Compressor
Stages Enabled
Factory Test
R/W
Coil
14
fac_test_en-
able
BV
91000
Select
Factory Reserved
Fan Mode Status
R
Input Register
(Float)
31
fan_-
mode_status
AV
51
Select
Network Status of the
Fan Mode Selection
0 = Start / Stop Fan
Operation
1 = Variable Frequency
Drive Fan Operation
Fan Output Cmd
R
Discrete Input
39
fan_cmd
BV
17
Select
Network Parameter to
set Fan Output Cmd
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Fan_mode
R/W
Holding Regis-
ter (Float)
19
fan_mode
AV
50
Select
Network Parameter to
set Fan Mode of Opera-
tion
1 = Standard Fan Config-
uration
2 = Variable Frequency
Drive Configuration (VAV
Default)
FILTER
R
Discrete Input
40
filter
BV
40
Select
Filter Status
0 = Normal
1 = Clean Filter
FRE
R
Discrete Input
41
frz_2st
BV
8
Select
UPM Board 1 Freeze
Alarm
0 = Normal
1 = Active Freeze Condi-
tion
FRE2
R
Discrete Input
42
frz_4st
BV
56
Select
UPM Board 2 Freeze
Alarm
0 = Normal
1 = Active Freeze Condi-
tion
High Static Count
Rst
R/W
Coil
23
rtn_sup_st-
c_ctr_rst
BV
99
Select
Network Parameter to
reset the high static
alarm counter Momen-
tary toggle ON/OFF to
reset counter
HP1
R
Discrete Input
43
hp1_2st
BV
5
nvoHp1Ala
rm
SNVT_switch(95)
UPM Board 1 High Pres-
sure Alarm Status for
Compressor 1
0 = Normal
1 = Active High Pressure
1 Alarm
Table 66 — Integration Points List (cont)
PROTOCOL MAP
MODBUS
BACNET
LONWORKS
OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME
SNVT
DESCRIPTION