81
C1_HAND
R
Discrete Input
9
comp1_hand
BV
151
Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C2_FAIL
R
Discrete Input
10
comp2_fail
BV
154
Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C2_HAND
R
Discrete Input
11
comp2_hand
BV
155
Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C3_FAIL
R
Discrete Input
12
comp3_fail
BV
157
Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C3_HAND
R
Discrete Input
13
comp3_hand
BV
158
Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C4_FAIL
R
Discrete Input
14
comp4_fail
BV
160
Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C4_HAND
R
Discrete Input
15
comp4_hand
BV
161
Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
CMP1_RNTM
R
Discrete Input
16
comp1_rntm
BV
35
Select
Compressor 1 Runtime
Alarm Status, (8760
Hours)
0 = Off
1 = Timer Has Expired
CMP2_RNTM
R
Discrete Input
17
comp2_rntm
BV
36
Select
Compressor 2 Runtime
Alarm Status, (Hours)
0 = Off
1 = Timer Has Expired
CMP3_RNTM
R
Discrete Input
18
comp3_rntm
BV
69
Select
Compressor 3 Runtime
Alarm Status (Hours)
0 = Off
1 = Timer Has Expired
CMP4_RNTM
R
Discrete Input
19
comp4_rntm
BV
71
Select
Compressor 4 Runtime
Alarm Status (Hours)
0 = Off
1 = Timer Has Expired
CO2 Sensor Ena
R/W
Holding Regis-
ter (Float)
9
co2_sen-
sor_ena
AV
26
Select
Zone CO
2
Sensor
Enable Setup
0 = No CO
2
(Default)
1 = CO
2
Monitoring
2 = CO
2
+ Damper
3 = CO
2
BAS Monitoring
4 = CO
2
BAS + Damper
5 = Open Damper as Fan
runs
Coil Configuration
Status
R
Input Register
(Float)
3
coil_cfg_sta-
tus
AV
150
Select
Network Status of Coil
Configuration
0 = Parallel
1 = Series
Comp Stage1 Out-
put Cmd
R
Discrete Input
20
cmp_stg1_cm
d
BV
11
nvoC-
mp1Cmd
SNVT_switch(95)
Compressor Stage 1
Output Status
0 = Compressor Stage 1
Off
1 = Compressor 1 On
Comp Stage2 Out-
put Cmd
R
Discrete Input
21
cmp_stg2_cm
d
BV
12
nvoC-
mp2Cmd
SNVT_switch(95)
Compressor Stage 2
Output Status
0 = Compressor 2 Off
1 = Compressor 2 On
Comp Stage3 Out-
put Cmd
R
Discrete Input
22
cmp_stg3_cm
d
BV
66
nvoC-
mp3Cmd
SNVT_switch(95)
Compressor Stage 3
Output Status
0 = Compressor 3 Off
1 = Compressor 3 On
Comp Stage4 Out-
put Cmd
R
Discrete Input
23
cmp_stg4_cm
d
BV
67
nvoC-
mp4Cmd
SNVT_switch(95)
Compressor Stage 2
Output Status
0 = Compressor 4 Off
1 = Compressor 4 On
Table 66 — Integration Points List (cont)
PROTOCOL MAP
MODBUS
BACNET
LONWORKS
OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME
SNVT
DESCRIPTION