Table 23 — VFD Factory Default Settings (cont)
ABB 550 DRIVE FACTORY CONFIGURATION VFD 1
GROUP NUMBER
PARAMETER NUMBER
DESCRIPTION
VALUE
3
0
3006
Motor Thermal Time
105
0
s
3007
Motor Load Curve
100%
3008
Zero Speed Load
70%
3009
Break Point Frequency
35Hz
301
0
Stall Function
NOT SEL
3011
Stall Frequency
20 Hz
3012
Stall Time
20 Sec
3017
Earth Fault
Enabled
31
3101
Number of Retries
5
3102
Trial Time
30Sec
3103
Delay Time
6 Sec
3104
AR Overcurrent
Enabled
3105
AR Overvoltage
Enabled
3106
AR Undervoltage
Enabled
3107
AR AI<Minimum
Disabled
3108
AR External Fault
(
0
) Disabled
34
3401
Signal Parameter 1
Output Freq
3402
Signal 1 Minimum
0
3403
Signal 1 Maximum
60 / 50 (Maximum motor operating Hertz)
3404
Output 1 DPS Form
0
3405
Output 1 DSP Unit
% SP
3406
Output 1 Minimum
0
3407
Output 1 Maximum
10
0
3408
Signal Parameter 2
Current (Motor Current Measured by the Drive)
3409
Signal 2 Minimum
0
341
0
Signal 2 Maximum
FLA + 15% A
3411
Output 2 DPS Form
0
3412
Output DSP Unit
A (2)
3413
Output 2 Minimum
0
3414
Output 2 Maximum
FLA + 15% A
3415
Signal Parameter 3
AI-1
3416
Signal 3 Minimum
0
3417
Signal 3 Maximum
1
0
3418
Output 3 DPS Form
0
3419
Output DSP Unit
V (2)
342
0
Output 3 Minimum
0
3421
Output 3 Maximum
1
0
4
0
4001
Gain
2
.
5
4002
Integration Time
3Sec
4005
Error Value Inver
NO
4006
Units
%
4007
Display Format
x
.
xxx
401
0
Setpoint Select
Internal
4012
Setpoint Minimum
0
V
4013
Setpoint Maximum
10V
4027
PID1 Parameter Set
SET1