29
LEGEND
Table 12 — Electrical Data — with Belt Drive Motor, Inverter Duty (50BVJ)
MODELS
RATED
VOLTAGE
VOLTAGE
MIN/MAX
COMPRESSOR
INDOOR FAN MOTOR
POWER SUPPLY
QTY
RLA
(EACH)
LRA
(EACH)
MOTOR
HP
MOTOR
QTY
FLA
(EACH)
MIN
CIRCUIT
AMPS
MAX FUSE/
HACR
20
208-230/3/60
197/253
2
29.5
195.0
2.0
2
6.2
78.8
100
208-230/3/60
197/253
2
29.5
195.0
3.0
2
8.8
84.0
110
208-230/3/60
197/253
2
29.5
195.0
5.0
2
13.5
93.4
110
460/3/60
414/506
2
14.7
95.0
2.0
2
3.1
39.3
50
460/3/60
414/506
2
14.7
95.0
3.0
2
4.3
41.7
50
460/3/60
414/506
2
14.7
95.0
5.0
2
6.2
45.5
60
575/3/60
518/632
2
12.2
80.0
2.0
2
2.0
31.5
40
575/3/60
518/632
2
12.2
80.0
3.0
2
3.5
34.4
45
24
575/3/60
518/632
2
12.2
80.0
5.0
2
4.5
36.5
45
208-230/3/60
197/253
2
30.1
225.0
2.0
2
6.2
80.1
110
208-230/3/60
197/253
2
30.1
225.0
3.0
2
8.8
85.3
110
208-230/3/60
197/253
2
30.1
225.0
5.0
2
13.5
94.7
110
460/3/60
414/506
2
16.7
114.0
2.0
2
3.1
43.8
60
460/3/60
414/506
2
16.7
114.0
3.0
2
4.3
46.2
60
460/3/60
414/506
2
16.7
114.0
5.0
2
6.2
50.0
60
575/3/60
518/632
2
12.2
80.0
2.0
2
2.0
31.5
40
575/3/60
518/632
2
12.2
80.0
3.0
2
3.5
34.4
45
28
575/3/60
518/632
2
12.2
80.0
5.0
2
4.5
36.5
45
208-230/3/60
197/253
2
48.1
245.0
3.0
2
8.8
125.8
150
208-230/3/60
197/253
2
48.1
245.0
5.0
2
13.5
135.2
175
460/3/60
414/506
2
18.6
125.0
3.0
2
4.3
50.5
60
460/3/60
414/506
2
18.6
125.0
5.0
2
6.2
54.3
70
575/3/60
518/632
2
14.7
100.0
3.0
2
3.5
40.0
50
34
575/3/60
518/632
2
14.7
100.0
5.0
2
4.5
42.1
50
208-230/3/60
197/253
2
55.8
340.0
5.0
2
13.5
152.6
200
460/3/60
414/506
2
26.9
173.0
5.0
2
6.2
72.9
90
FLA
— Full Load Amps
HP
— Horsepower
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps