45
*Refer to Motor name plate.
Table 22 — VFD Factory Default Settings
ABB 550 DRIVE FACTORY CONFIGURATION VFD 1
GROUP NUMBER
PARAMETER NUMBER
DESCRIPTION
VALUE
99
9902
Application Macro
HVAC Default
9904
Motor control Mode
Scalar
9905
Motor Nominal Voltage
9906
Motor Nominal Current
9907
Motor Nominal Frequency
9908
Motor Nominal Speed
9909
Motor Nominal Power
1
0
1001
EXT1 Commands
DI1 - Start/Stop
1002
EXT2 Commands
N/A
1003
Direction
Forward
11
1103
REF1 Select
AI-1
1104
REF1 Minimum
0Hz at 60Hz/ 0Hz at 50Hz
1105
REF 1 Maximum
60 Hz at 60Hz / 50 Hz at 50Hz
12
1201
Constant Speed Select
NOT SEL
1202
Constant Speed Value (Field
Programmable)
6Hz
-
Motor Nominal Frequency
13
1301
Minimum AI-1
0
%
1302
Maximum AI-1
100%
1303
Filter AI-1
1 Sec
1304
Minimum AI-2
0
%
1305
Maximum AI-2
100%
1306
Filter AI-2
1 Sec
14
1401
Relay Output 1
Ready
1402
Relay Output 2
Run
1403
Relay Output 3
Fault (Inverted)
15
1507
AO2 Content
AI-1 (Used to control VFD2 Reference)
1508
AO2 Content Min
0
%
1509
AO2 Content Max
100%
151
0
Minimum AO2
0.0
mA
1511
Maximum AO2
20
.0
mA
1512
Filter AO2
1 Sec
16
1601
Run Enable
DI-1
1608
Start Enable 1
DI-4
1609
Start Enable 2
N/A
2
0
2002
Minimum Fan Speed
0
2003
Maximum Current
30% higher that Motor (s) FLA
2007
Minimum Frequency
0Hz
2008
Maximum Frequency
60Hz / 50Hz (Per motor frequency rating)
21
2101
Start Function
Fly Start
2102
Stop Function
Coast
22
2202
Accelerate Time
30 Seconds
2203
Decelerate Time
30 Seconds
26
2605
Volt/ Freq Ratio
Square
2606
Switching Frequency
4Khz
2607
Switching Frequency Control
ON