86
Low Ambient Cooling Operation down to 40
_
F (4
_
C)
In Low Ambient RTU conditions when the temperature is between 55
_
F (13
_
C) and 40
_
F (4
_
C), the Low Ambient Switch
(LAS) will be active and the outdoor-fans will run to the pre-set factory outdoor-fan speed. When the temperature is
greater than 65
_
F (18
_
C), the Low Ambient Switch will deactivate and the outdoor-fans will run in the standard cooling
mode. If the Outdoor Fan Select Switch (see Fig. 71) is in the up position, the outdoor fans will run in the Fan Cycle
Speed Mode (FCS) set to 250 rpm. If the Outdoor Fan Select Switch is in the down position, the outdoor fans will run in
the Minimum Fan Speed Mode (MIN) set to 160 rpm regardless of the cooling demand.
OF SPEED
SELECT
UP
FCS
MIN
DOWN
C13327
Fig. 71 -- Outdoor Fan Speed Select Switch
LC size 007 units have a SPST normally open Low Ambient Switch wired across the TS and OF terminal and a jumper
placed across the PS terminal (See Fig. 72). When the LAS is active, the switch will close making contact to the OF
terminal. This is done for units that require all outdoor fans to run at the same pre-set factory Low Ambient Speed.
LC Size 008 through 012 Units have a SPDT Low Ambient Switch wired to the OF terminal and the Outdoor Fan Relay
(See Fig. 73). The jumper across the PS terminal will be removed. When the LAS is active, the switch will close making
contact to the OF terminal and will drop connection to the ODF Relay. When electrical connection is removed from the
ODF Relay, the PS connection will be opened. This will place the third outdoor-fan electrically isolated from receiving
any speed command, which will then turn the motor off. This is done for units that only require two outdoor fans to run
at the same pre-set factory Low Ambient Speed.
JUMPER ON
LAS
SPST
PS
PS
TS
OF
C13328
Fig. 72 -- Schematic of SPST Low Ambient Switch
LAS
SPST
PS
PS
OF
REMOVE JUMPER
ODF RELAY
24VAC
TB-4
C13329
Fig. 73 -- Schematic SPDT Low Ambient Switch
The Low Ambient Outdoor Fan Control chart (listed below) shows the operation of the outdoor fans for each unit
Low Ambient Temperature Outdoor Fan Control
LC
Size
No. of Fans On
No. of Fans Off
Switch
LAS
FIG. No.
OF Select Switch
RPM
007
2
0
(1) SPST
72
Up
250
008
2
1
(1) SPDT
73
Down
160
009
2
1
(1) SPDT
73
Down
160
012
2
1
(1) SPDT
73
Down
160
Heating
In the Heating Mode (W1 on the thermostat), power is applied to the G and W1 terminal at the ISC board and energizes the
first state of electric heat. Upon more call for heat (W2 at the thermostat), power is applied to the G and W2 terminal at
the ISC board and energizes the second state of electric heat. The VFD controlled indoor fan will operate at high speed
regardless of the heating demand.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...