37
Integrated Staging Control (ISC) Board
DDC
Control
Indoor Fan
“On” Status
IGC
Board
Power
Plug
Phase
Monitor
Relay
Auxilary
Shutdown
Condensate
Overflow
Economizer
Occupancy
Status Code LEDs
Thermostat
DDC
Control
Remote
Shutdown
Smoke
Shutdown
Smoke
Alarm
Low Ambient
Outdoor Fan
Control
Compressors
Reheat
Low Pressure
Switch
High Pressure
Switch
Indoor Fan
Motor
Outdoor Fan
Motors
Phase
Monitor
Relay
C13673
Fig. 50 -- Integrated Staging Control (ISC) Board
ISC Board -- Sequence of Operation
General —
The Carrier Integrated Staging Control (ISC) is intended
for use with a standard thermostat or direct digital control
(DDC) capable of three cooling stages. After initial power
to the board, a Green LED will blink with a 1 second duty
cycle indicating the unit is running properly. In the event
of the ISC board failing, the Green LED will be OFF or
continuously ON. When the unit is not running properly,
the Green LED will blink along with Red LED lights. The
Red LED light configuration will indicate the type of
error the board has identified. See Fig. 50 for LED
locations and Table 7 for a list of status codes.
The ISC board can be remotely shutdown by removing
Jumper 4 and wiring to the Remote Shutdown terminal.
The Smoke Control Module can shutdown the unit by
removing Jumper 3 and wiring to the Smoke Shutdown
terminal. The Smoke Alarm terminal on the ISC Board
provides a pass thru connection should a smoke alarm
signal be connected. In the case of the RTU Open option,
the RTU Open controller provides the signal which is
passed thru the ISC board to the Smoke Alarm terminal.
The crankcase heater will run at all times except when the
compressors are running. An auxiliary power supply
(24Vac) available at TB--4 Terminal is provided to power
auxiliary equipment. An optional Phase Monitor Relay
can be wired to the PMR terminal by removing Jumper 5.
An optional Condensate Flow Switch can be wired to the
COFS Terminal by removing Jumper 7.
Ventilation —
In the Ventilation/Fan Mode (G on the thermostat), the
indoor--fan will run at low speed and the damper will
operate at minimum position.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...