39
require all outdoor fans to run at the same pre--set factory
Low Ambient Speed.
OF SPEED
SELECT
UP
FCS
MIN
DOWN
C13327
Fig. 51 -- Outdoor Fan Speed Select Switch
JUMPER ON
LAS
SPST
PS
PS
TS
OF
C13328
Fig. 52 -- Schematic of SPST Low Ambient Switch
The Low Ambient Temperature Outdoor Fan Control
Table (below) shows the operation of the outdoor fan for
size 07 units.
Table 8 – Low Ambient Temperature Outdoor Fan Control
LC Size
No. of
Fans On
No. of
Fans Off
Switch
Outdoor Fan
Select Switch
RPM
07
2
0
SPST
Up
250
08
2
1
(1)
SPDT
Down
160
09
2
1
(1)
SPDT
Down
160
12
2
1
(1)
SPDT
Down
160
Heating —
In the Heating Mode (W1 on the thermostat), power is
applied to the G and W1 terminal at the ISC board and
energizes the first state of electric heat. Upon more call
for heat (W2 at the thermostat), power is applied to the G
and W2 terminal at the ISC board and energizes the
second state of electric heat. The VFD controlled indoor
fan will operate at high speed regardless of the heating
demand.
EconoMi$er X (Factory--Installed Option)
IMPORTANT:
Any economizer that meets the economizer require-
ments as laid out in California’s Title 24 mandatory section 120.2
(fault detection and diagnostics) and/or prescriptive section 140.4
(life--cycle tests, damper leakage, 5 year warranty, sensor accuracy,
etc), will have a label on the economizer. Any economizer without
this label does not meet California’s Title 24. The five year limited
parts warranty referred to in section 140.4 only applies to factory in-
stalled economizers. Please refer to your economizer on your unit.
EconoMi$er X is an ultra low leak economizer system
which is available for 50LC 07--12 units.
The factory--installed option consists of:
S
Low leak economizer damper assembly
S
Direct--drive damper actuator with local equipment bus
communications
S
W7220 economizer controller with keypad and display
S
Supply Air Temperature sensor (20K ohm)
S
Outdoor changeover condition sensor (either 20K ohm
dry--bulb or enthalpy sensor)
Unit Installation —
All damper hardware and standard economizer control
components except the enthalpy sensor are factory--mounted
in their operating location. Complete the unit installation by
relocating the enthalpy sensor (when provided; see below),
then assembling and mounting the unit’s outside air hood.
Refer to the base unit’s installation instruction manual for
directions on locating the hood parts package and
assembling the hood with filters.
Enthalpy Sensor Relocation —
See Fig. 61 for view of the enthalpy sensor. Locate the
enthalpy sensor on the side of the economizer housing;
remove mounting screws and save screws. Confirm the DIP
switches are set at OFF, OFF, OFF (see Table 16). Move the
enthalpy sensor to the front face of the economizer housing
and mount per label.
W7220 Economizer Controller
The economizer controller used on electro mechanical units
is the Honeywell W7220.
The W7220 provides typical economizer functions,
including:
S
Management of outside air damper for base unit
Occupied (damper open and modulating) and unit OFF
or Unoccupied status (damper closed)
S
Free--cooling using all outside air when outdoor
conditions permit Integrated cooling operation using
outside air and mechanical cooling when required
S
Demand Control Ventilation (DCV) for modulating
ventilation airflow according to space CO
2
level
(requires factory--option or field--installed CO
2
sensor)
The W7220 control also includes a new capability that will
adjust the damper control points during DCV or minimum
ventilation operation as the indoor fan speed is changed.
This control function ensures that required space ventilation
airflow quantities are maintained during reduced fan speed
operation.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...