Table 19 – W7220 Input’/Output with Demand Control Ventilation (DCV)
INPUTS
Ref:
FAN
SPD
(a)
OUTPUTS
DEMAND
CONTROL
VENTILATION
OUTSIDE AIR
Good to
economize?
Y1---I
Y2---I
Mechanical Cooling Stage
Occupancy
OCC Yes
OCC No
Y1---O/1ST
Y2---O/2ND
Outside Air Damper Position
Below set
No
Off
Off
Low
0---v/Off
0---v/Off
VENTMIN L
Closed
On
Off
Low
24---v/On
0---v/Off
VENTMIN L
Closed
On
On
High
24---v/On
24---v/On
VENTMIN H
Closed
Yes
Off
Off
Low
0---v/Off
0---v/Off
VENTMIN L
Closed
On
Off
Low
0---v/Off
0---v/Off
Modulating:
VENTMIN L to
Full---Open
Modulating:
Closed to
Full---Open
On
On
High
2SP DELAY (b);
24v/On
0---v/Off (c)
Modulating:
VENTMIN H to
Full---Open
Modulating:
Closed to
Full---Open
Above set
No
Off
Off
Low
0---v/Off
0---v/Off
Modulating:
VENTMIN L to
VENTMAX L
Closed
On
Off
Low
24---v/On
0---v/Off
Modulating:
VENTMIN L to
VENTMAX L
Closed
On
On
High
24---v/On
24---v/On
Modulating:
VENTMIN H to
VENTMAX H
Closed
Yes
Off
Off
Low
0---v/Off
0---v/Off
Modulating:
VENTMIN L to
VENTMAX L
Closed
On
Off
Low
0---v/Off
0---v/Off
Modulating:
VENTMIN L to
Full---Open
Modulating:
Closed to
Full---Open
On
On
High
2SP DELAY (b);
24v/On
0---v/Off (c)
Modulating:
VENTMIN H to
Full---Open
Modulating:
Closed to
Full---Open
(a)
Fan Speed for reference only; tins is not an input or output function of the W7220
(b)
See Menu ADV SETUP ---> 2SP FAN DELAY for details
(c)
See Menu ADV SETUP ---> STG# DLY. With Stage 3 delay enabled, control can turn on 2
nd
stage of cooling Y2---O after delay if the call for Y2---I has not
been satisfied.
As space temperature falls, the thermostat will remove its
call for second stage cooling; ISC terminal Y2 call is
removed. The supply fan motor remains High Speed. The
outside air damper limit is repositioned to between MIN
POS L and 100% open. Second stage cooling (Compressor
1 operation) stops. As space temperature continues to fall
and space cooling load is satisfied, the thermostat will
remove its call for first stage cooling; ISC terminal Y1
call is removed. The W7220 input Y1--I is removed; free
cooling mode ends. Outside air damper will remain at
MIN POS L if supply fan remains in operation (CONT
FAN) or to closed if supply fan stops (AUTO FAN).
Should 100% outside air and second stage cooling
(Compressor 1 operation) not be capable of satisfying the
space cooling load, space temperature will rise and the
thermostat will call for third stage cooling: ISC terminal
Y3 is also energized, starting third stage cooling
(Compressor 2 operation). The supply fan motor will
remain at High Speed. The Y3 demand is received at
W7220 input Y2--I. The outdoor air damper position will
modulate from MIN POS H to 100% Open to maintain
SAT at MAT SET concurrent with Compressor 2
operation.
As space temperature falls, the thermostat will remove its
call for third stage cooling; ISC terminal Y3 call is removed.
The supply fan will remain at High Speed. The W7220 input
Y2--I is also removed; the outside air damper is repositioned
to modulate from MIN POS L to 100% Open, third stage
cooling (Compressor 2 operation) stops.
Power Exhaust:
If accessory power exhaust is installed,
the power exhaust fan motors will be energized by the
economizer control as the dampers open above the
setpoint EXH1 SET L during Low Speed operation or
EXH1 SET H during High Speed fan operation. The
EXH1 output will be de--energized as the dampers close
below the EXH1 setpoint value.
Damper movement from full closed to full open (or vice
versa) will take approximately 1--
1
/
2
minutes.
Heating With EconoMi$er X —
When the space temperature calls for heat (W1 closes),
ISC terminal W1 is energized. The supply fan will start
and run in High Speed. The W1 signal will connect
toW7220 input AUX2I; the outside air damper will move
to MIN POS H. Unit heating sequence will follow base
unit control sequences.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...