64
change the language, press the
OK
key and use the
Y
and
B
keys to scroll to the desired language and then
press
OK
.
Off
Reset
Hand
On
Alarm
Warn.
On
Com.
OK
Ba
ck
Auto
On
Status
Menu
Quick
Menu
Main
Menu
Select language English
[0] English
SETUP 1
C13119
Fig. 70 -- Keypad with Power Up Screen Displayed
2. Selecting Regional Settings:
a. Press the
Off Reset
key.
b. Press the
Menu
key to move the
B
(triangle
icon) so it is positioned over Main Menu. The
display show the following --
0---** Operation / Display
1---** Load and Motor
c. Press the
OK
key, the display changes to --
0---0* Basic Settings
0---1* Set---up Operations
d. With the top row highlighted, press
OK
. The
display changes to --
0---01 Language
[0] English
NOTE
: If English is not the desired language press
OK
,
select the desired language and press
OK
again.
e. Press
B
(
Down Arrow
key) once; the display
changes to --
0---03 Regional Settings
[0] International
f. Press
OK
; the [0] is now highlighted.
g. Press
B
(
Down Arrow)
key once; the display
changes to --
0---03 Regional Settings
[1] North America
h. Press
OK
NOTE
: If the Alarm 060 appears, follow Step 3 to clear
the alarm. Make sure to press
Off Reset
when done. If
there is no alarm, continue at Step 4.
3. Clearing Alarm 060: External Interlock:
a. Press the
Menu
key twice to position the
B
(tri-
angle icon) over Main Menu; the display
changes to --
0---** Operation / Display
1---** Load and Motor
b. Press the
B
(
Down Arrow)
key until the follow-
ing display appears --
4---** Limits / Warnings
5---** Digital In/Out
c. Press
OK
. The display changes to --
5---0* Digital I/O mode
5---1* Digital Inputs
d. Press
B
(
Down Arrow)
once to highlight the bot-
tom row and press
OK
. The display changes to --
5---10 Terminal 18 Digital In…
[8] Start
e. Press
B
(
Down Arrow)
twice; the following
display appears--
5---12 Terminal 27 Digital In…
[7] External Interlock
f. Press
OK
to highlight the number in the bracket.
g. Press
B
(
Down Arrow)
until the following display
appears --
5---12 Terminal 27 Digital In…
[0] No operation
h. Press
OK
.
i. Press
Off Reset.
The Alarm indicator disappears.
4. Entering Grid Type:
a. Press the
Menu
key to move the
B
(triangle
icon) so it is positioned over Main Menu. The
display show the following --
0---0* Basic Settings
0---1* Set---up Operations
b. Press
OK
twice: the display changes to --
0---01 Language
[0] English
c. Press
B
(
Down Arrow)
three times, to reach the
following display --
0---06 Grid Type
[102] 200---240V/60Hz
d. Press
OK
to highlight the number in the bracket
and then use the
Y
and
B
(
Up
and
Down
Arrow
) keys to select the desired voltage and
Hertz for the unit.
e. Press
OK
to accept the selection and continue.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...