49
To determine the damper setpoint position, perform the
following procedure for each condition setpoint, with
mechanical cooling OFF:
Calculate the appropriate supply air temperature using the
following formula:
TS = (TO x Vbz/CFM) + TR x (CFM – Vbz)/CFM
TS = Supply Air Temperature
TO = Outdoor Air Temperature
Vbz = Design Maximum Ventilation CFMr
CFM= Unit Supply Airflow Rate
TR = Return Air Temperature
As an example:
Unit Airflow Rate at High Speed is 4000 CFM
Ventilation CFM at design occupancy Vbz is 1200 CFM
TO = 60 F
TR = 75 F
Required TS = 60 x (1200/4000) + 75 x (4000 – 1200/4000)
= 60 x 0.30 + 75 x 0.70 = 18.0 + 52.5
= 70.5
At the W7220 keypad, enter the parameter SETUP -->
VENTMAX H and adjust the setpoint value until the
observed Supply Air Temperature (MA TEMP) reaches
70.5. Press the
“Enter” key to save this setpoint to
controller memory.
When determining VENTMIN setpoints, substitute the
value for Va in place of Vbz in the formula.
DCV Setpoint:
The SETPOINTS parameter DCV SET
defines the space CO
2
level above which the DCV mode
begins to open the outside air damper beyond its
VENTMIN ventilation lower limit. This setpoint should
be a minimum of 100 ppm greater than the outdoor
ambient CO
2
level to ensure the outside air will be
capable of diluting the space CO2 level. A typical value
for outdoor CO
2
is 400 ppm; adjust the setpoint DCV SET
to 500 ppm if outdoor CO
2
level is not known. The
factory default value for DCV SET is 1100 ppm.
Economizer Occupancy Control —
The 24--v signal that terminates at the W7220’s OCC
input to place the economizer control in Occupied mode
when the supply fan starts is routed through the rooftop
unit’s Integrated Staging Control
Board at its
OCCUPANCY jumper. To implement an occupancy
control for the economizer operation, connect a contact
set at ISC OCCUPANCY quick--connect terminals and cut
jumper JMP1. To allow automatic occupancy mode, close
the control contacts. To place the economizer in
Unoccupied mode, open the control contacts.
CUT JUMPER JMP1
TO IMPLEMENT
OCCUPANCY
CONTROL
OCCUPANCY
TERMINALS
C13674
Fig. 60 -- Integrated Staging Control Board (ISC) -- Occupancy Terminals and Jumper
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...