48
Demand Control Ventilation —
Demand Control Ventilation (DCV) function requires a
space air CO
2
sensor be connected to the W7220
controller. The CO
2
sensor provides a 2 to 10 vdc signal
proportional to the space CO
2
level. This sensor is
available as a factory--installed option (located in the
unit’s return air plenum) or as a field--installed accessory.
See Fig. NO TAG for model number nomenclature; check
Position #9 for codes E, F, G or H indicating a
factory--installed CO
2
sensor. The W7220 automatically
recognizes the connection of this sensor and self--enables
the DCV function after the Configuration period.
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
INCREASING VENTILA
TION
VENTMAX
VENTMIN
100
700
INSIDE OUTSIDE CO
2
DIFFERENTIAL
C12167
Fig. 58 -- DCV Single--Speed System Setpoints
DCV With Single--Speed Fan System:
During DCV, the
outside air damper modulates between two user
configurations depending upon the signal level of the
space or return air CO
2
sensor representing the space
occupancy level. The lower of these two positions is
referred to as the Minimum IAQ Damper Position
(designated VENTMIN) while the higher is referred to as
Economizer Minimum Position (designated MINIMUM
POSITION or VENTMAX). The VENTMIN position
should be set to an economizer position that brings in
enough fresh air to remove contaminants and CO
2
generated by sources other than people; this airflow rate is
designated Va. The VENTMAX should be set to an
economizer position that brings in enough fresh air to
remove contaminants and CO
2
generated by all sources
including people at the design condition for maximum
space occupancy; this airflow rate is designated Vbz.
DCV With Two--Speed Fan System:
Ventilation codes
require that the same ventilation rates (Vbz and Va,
expressed as CFM) be provided regardless of supply fan
speed. When the supply fan speed is reduced, the internal
static pressure in the unit’s return plenum also decreases.
If the same outside air damper position is retained, the
airflow rate through the OA damper decreases below the
Va and Vbz levels. To restore ventilation rates to design
levels, the damper positions VENTMIN and VENTMAX
must be automatically adjusted when the fan speed
changes. The W7220 provides this function when it is
configured for 2--speed fan operation through a second set
of damper position setpoints.
During operation at High fan speed, the damper setpoint
limits are designated VENTMIN H and VENTMAX H.
Damper operation is same
as described under
Single--Speed Fan above.
During operation at Low fan speed, the damper setpoint
limits change to VENTMIN L and VENTMIN L. These
settings are higher than the comparable High speed
settings and cause the outside air damper to open more to
allow the same Va and Vbz airflow rates to be admitted to
the space.
Adjust the DCV setpoints VENTMAX H and VENTMAX L
with supply fan speed in High speed and Low speed
respectively to provide the design load ventilation airflow
rate Vbz by measuring outside air temperature, return air
temperature and supply air temperature. Make damper
position adjustments with at least 10
_
F temperature
difference between the outdoor and return--air temperatures.
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
INCREASING VENTILA
TION
VENTMAX H
VENTMIN H
100
700
INSIDE OUTSIDE CO
2
DIFFERENTIAL
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
INCREASING VENTILA
TION
VENTMAX L
VENTMIN L
100
700
INSIDE OUTSIDE CO
2
DIFFERENTIAL
HIGH SPEED FAN
LOW SPEED FAN
C12168
Fig. 59 -- DCV 2--Speed System Setpoints — Same Ventilation CFM at Both Speeds
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...