Table 9 -- Menu Structure
a
(cont)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
STATUS
EXH2 OUT
OFF
ON/OFF
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX terminal; displays only if AUX = EXH2
ON = relay closed
OFF = relay open
MECH COOL ON
0
0, 1, or 2
Displays stage of mechanical cooling that is active.
FAN SPEED
n/a
LOW or HIGH
SUPPLY FAN SPEED
Displays speed setting of fan on a 2---speed fan unit.
W (HEAT ON)
n/a
ON/OFF
HEAT DEMAND STATUS
Displays status of heat demand on a 2---speed fan unit.
SETPOINTS
MAT SET
53
_
F
(12
_
C)
38 to 65
_
F;
(3 to 18
_
C)
increment by 1
SUPPLY AIR SETPOINT
Setpoint determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
See Menu Note 2.
LOW T LOCK
32
_
F
(0
_
C)
---45 to 80
_
F;
(---43 to 27
_
C)
increment by 1
COMPRESSOR LOW TEMPERATURE LOCKOUT
Setpoint determines outdoor temperature when the mechanical cooling
cannot be turned on.
DRYBLB SET
63
_
F
(17
_
C)
48 to 80
_
F
(9 to 27
_
C)
increment by 1
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoint determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63
_
F (17
_
C), unit will
economize at 62
_
F (16.7
_
C) and below and not economize at 64
_
F
(17.8
_
C) and above. There is a 2
_
F (1.1
_
C)deadband.
See Menu Note 3
ENTH CURVE
ES3
ES1, ES2, ES3, ES4, or
ES5
ENTHALPY CHANGEOVER CURVE
(Requires enthalpy sensor option)
Enthalpy boundary “curves” for economizing using single enthalpy.
DCV SET
1100ppm
500 to 2000 ppm;
increment by 100
DEMAND CONTROL VENTILATION SETPOINT
Displays only if CO
2
sensor is connected. Setpoint for Demand Control
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
MIN POS L
6.0 V
2 to 10 Vdc
VENTILATION MINIMUM POSITION AT LOW SPEED
Displays ONLY if a CO
2
sensor is NOT connected.
MIN POS H
4.4 V
2 to 10 Vdc
VENTILATION MINIMUM POSITION AT HIGH SPEED
Displays ONLY if a CO
2
sensor is NOT connected.
VENTMAX L
6.0 V
2 to 10 Vdc
DCV MAXIMUM DAMPER POSITION AT LOW SPEED
(Requires CO
2
sensor connected)
VENTMAX H
4.4 V
2 to 10 Vdc
DCV MAXIMUM DAMPER POSITION AT HIGH SPEED
(Requires CO
2
sensor connected)
VENTMIN L
3.7 V
2 to 10 Vdc
DCV MINIMUM DAMPER POSITION AT LOW SPEED
(Requires CO
2
sensor connected)
VENTMIN H
2.8 V
2 to 10 Vdc
DCV MINIMUM DAMPER POSITION AT HIGH SPEED
(Requires CO
2
sensor connected)
EXH1 L SET
65%
0 to 100%;
Increment by 1
EXHAUST FAN STAGE 1 SETPOINT AT LOW SPEED
Setpoint for OA damper position when exhaust fan1 is powered by the
economizer
EXH1 H SET
50%
0 to 100%;
Increment by 1
EXHAUST FAN STAGE 1 SETPOINT AT HIGH SPEED
Setpoint for OA damper position when exhaust fan1 is powered by the
economizer
EXH2 L SET
80%
0 to 100%;
Increment by 1
EXHAUST FAN STAGE 2 SETPOINT AT LOW SPEED
Setpoint for OA damper position when exhaust fan1 is powered by the
economizer. Only used when AUX1---O is set to EHX2.
EXH2 H SET
75%
0 to 100%;
Increment by 1
EXHAUST FAN STAGE 2 SETPOINT AT HIGH SPEED
Setpoint for OA damper position when exhaust fan1 is powered by the
economizer. Only used when AUX1---O is set to EHX2.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...