CONTROL SET POINT AND CONFIGURATION LOG
Project Name/Location:
Model Number:
Serial Number:
Date:
Technician
Menu Tables:
1. SYSTEM SETUP
2. ADVANCED SETUP
3. SETPOINTS
Menu 1: System Setup
Parameter
Project
Value
Parameter
Default
Value
Parameter
Range and Increment
Notes
INSTALL
01/01/10
Display order = MM/DD/YY
Setting order = DD, MM, then YY
UNITS DEG
_F
_F or _C
Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT
CONV
CONV required for
2---speed mode
CONV = conventional;
HP O/B = Enable Heat Pump mode; not available with 2---speed
See Menu Note 4 (on page 44)
AUX2 I
W
W required for
2---speed mode
W = Informs controller that system is in heating mode.
SD = Enables configuration of shutdown (not available on 2---speed)
See Menu Note 4 (on page 44)
FAN TYPE
2speed
2speed required
Sets the economizer controller for operation of 1 speed or 2 speed
indoor fan system.
See Menu Note 4 (on page 44)
FAN CFM
5000cfm
100 to 15000 cfm;
UNIT DESIGN AIRFLOW (CFM)
Enter ONLY if using DCVCAL ENA = AUTO
The value is found in the Project Submittal documents for the specific
RTU.
AUX OUT
NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
ERV = Energy Recovery Ventilator
EXH2 = second damper position relay closure for second exhaust fan
SYS = use output as an alarm signal
OCC
INPUT
INPUT or ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 Vac), the
24---Vac is input to the OCC terminal. RTU control circuit provides
24---Vac to OCC through OCCUPIED terminals on Integrated Staging
Control Board. (see Menu Note 2 (on page 44)
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD will
briefly flash YES and change to NO but all parameters will change to
the factory default values.
RECHECK AUX2 I and FANTYPE for required 2---speed values.
Содержание 50LC 07
Страница 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Страница 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Страница 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Страница 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Страница 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Страница 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Страница 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Страница 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Страница 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Страница 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Страница 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Страница 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...