Model 601GAS burner — Instruction manual
MN601GAS 012516
– 28 –
Where appliance instructions differ from this manual, follow the appliance instructions.
9. Dimensions and mounting information
Figure 13
Dimensional data (shown with straight gas train)
Mounting burner to appliance
Positive overfire pressure applications: When firing with
positive overfire pressure, do not exceed the pressure
specified in the appliance manual.
Positive overfire pressure reduces maximum burner capac-
ity. See Table 1a notes for estimated reduction in burner
capacity with pressurized firing.
When using the adjustable flange, follow the steps in Fig-
ure 14 to prepare for pressurized firing.
Failure to comply could result in severe personal injury,
death or substantial property damage.
When using a welded flange burner, verify the insertion depth on the
appliance and burner (see page 10).
If using the adjustable flange (Figure 14), measure the appliance inser-
tion depth to the set the position of the flange on the air tube. Tighten
the flange locking screws firmly. Prepare the appliance opening to the
dimensions shown in Figure 14. Also read page 10.
Figure 14
Adjustable flange mounting information
1
Carlin 60200FR primary
2
Air tube
3
Flange (welded shown)
4
Carlin 41000 ignitor
5 Motor
6
Cast aluminum housing
7
Air flow switch
8
Gas connection, 1", 1¼", 1½" or 2" NPT
9
Gas pressure regulator
10 Low gas pressure switch
11 Secondary gas valve
12 Primary gas valve
13 High gas pressure switch
14 Manual gas cock
15 Orifice nipple