Model 601GAS burner — Instruction manual
MN601GAS 012516
– 19 –
Where appliance instructions differ from this manual, follow the appliance instructions.
4. Check System • Start-up Burner/Appliance
(continued)
The 60200FR stores in
formation from the last 50 fault
cycles in a fault log with 1 being the latest fau
lt
Fault Message
• The message that accompanied this fault
• If it was a Lockout message, the cycle is faulted
End State
• The last operating state before returning to Standby
• If not Post Purge or Flame Proven, the cycle is faulted
Flame Rod µA
• The FR current on entry to Lockout or Standby
• If the FR current is outside its limits, the cycle is faulted
Line Volts
• Running average of detected Line Volts at end of CFH cycle
• If <102 or >132, cycle is faulted
Motor Current
• “ - ” if current has not been determined yet
• “Ok” if current is known and above limit
• “Low” if current is known and below limit
Low current causes the cycle to be faulted
Ignitor Current
• “ - ” if current has not been determined yet
• “Ok” if current is known and above limit
• “Low” if current is known and below limit
Low current causes the cycle to be faulted
Valve Current
• “ - ” if current has not been determined yet
• “Ok” if current is known and above limit
• “Low” if current is known and below limit
Low current causes the cycle to be faulted
Recycle
• “Yes” if a recycle occurred in CFH cycle
A recycle causes the cycle to be faulted
• “No”
Run time
• Time motor output is on during this cycle
Burn time
• Time valve output is on during this cycle
CFH Cycle, enter at this row on column change
• The CFH cycle during which this fault occurred
• “1” if first cycle after baseline was reset
The 60200FR stores operating history
The first line contains the parameter listed below.
The second line contains the Value and Units if appropriate.
Lines starting with “Total” are not reset by Baseline Reset.
All other lines are reset using “Reset Baseline” setpoint.
“Fault Cycles”
• Number of fault cycles in log (50 max, then oldest is discarded)
“Total Cycles”
• Total Number of CFH cycles since control was put into service
“Total Run Time” (Motor on)
• Total Motor on time since control was put into service
“Total Burn Time” (Valve on)
• Total Valve on time since control was put into service
“Total On time”
• Total time since control was put into service
“Baseline time”
• Elapsed time since baseline was reset
“Max Line Volts”
• Highest line volts recorded since baseline reset
“Min Line Volts”
• Lowest line volts recorded since baseline reset
“Recycles”
• Total Recycles since baseline reset
“Run Time” (Motor on)
• Total Motor on time since baseline reset
“Burn Time” (Valve on)
• Total Valve on time since baseline reset
“CFH Cycles”
• Number of CFH cycles since baseline was reset
Operating and Fault History – 60200FR