5
powerSplit manual - cod. +030220320 rel. 1.1 - 09/12/02
Faston 1: C relè compressore
250 Vac 16 A 2 Hp max
Faston 2: NO relè compressore
Faston 3: C relè defrost
250 Vac 16 A res. max
Faston 4: NC relè defrost
Faston 5: NO relè defrost
Faston 8: C relè ventilatori
250 Vac 10 A res. (2 A) max
Faston 9: NO relelè ventilatori
Faston 13: C relè aux1/luce
250 Vac 16 A res. 500W-1000VA max
Faston 14: NO relè aux1/luce
Faston 6: C relè aux2/antiapp.
250 Vac 10 A res. (2 A) max
Faston 7: NO relè aux2/antiapp.
Faston 10: C relè allarme
250 Vac 10 A res. (2 A) max
Faston 11: NC relè allarme
Faston 12: NO relè allarme
2.1.3 Ingressi sonde NTC
• ingressi di misura per sonde NTC standard Carel (10 Kohm a 25 ˚C)
• compatibilità con misura PLUG IN, misura da -50 a +90 ˚C
• filtro ingresso 1mS (disturbi veloci, burst), la misura è filtrata SW con
media (/2 da 0,1 a 2s circa)
• connessione con morsetti fissi a vite per filo da 0,5 a 1,5 mm
2
.
• distanza max 30 m per compatibilità normative (surge)
Morsetto 24: ingresso segnale NTC sonda regolazione (ambiente)
(-50/+90˚C )
Morsetto 25: riferimento segnale NTC sonda regolazione
Morsetto 26: ingresso segnale NTC sonda defrost (-50/+90˚C)
Morsetto 27: riferimento segnale NTC sonda defrost
Morsetto 28: ingresso segnale NTC sonda prodotto/defrost 2 (-50/+90˚C)
Morsetto 29: riferimento segnale NTC sonda prodotto/defrost 2
2.1.4 Ingressi digitali
• ingressi da contatto pulito (non alimentato) con corrente di chiusura
8-12 mA
• filtro ingresso 1mS (disturbi veloci, burst), il segnale è filtrato SW
media a 240mS
• connessione con morsetti fissi a vite per filo da 0,5 a 1,5 mm
2
.
• distanza max 30 m per compatibilità normative (surge)
Morsetto 31: ingresso digitale 1
Morsetto 30: riferimento ingresso digitale 1
Morsetto 33: ingresso digitale 2
Morsetto 32: riferimento ingresso digitale 2
Note: l'utilizzo degli ingressi è programmabile da parametri (ingresso
multifunzione)
2.1.5 Ingresso sensore presenza luce
• ingresso da fotoresistenza per segnalare l'apertura delle porte in
armadi refrigerati, uno o due sensori previsti
• connessione con morsetti fissi a vite (2 vie) per filo da 0,5 a 1,5 mm
2
.
• Distanza massima 30 metri, per compatibilità normative (surge).
Morsetto 34: riferimento (comune) fotoresistenze
Morsetto 35: ingresso fotoresistenze (presenza luce)
Nota: è disponibile un solo ingresso con la possibilità di collegare uno
o due sensori in parallelo
Faston 1: C compressor relay
250Vac 16A 2 HP max
Faston 2: NO compressor relay
Faston 3: C defrost relay
250Vac 16A res. max
Faston 4: NC defrost relay
Faston 5: NO defrost relay
Faston 8: C fan relay
250Vac 10A res. (2A) max
Faston 9: NO fan relay
Faston 13: C aux1/light relay
250Vac 16A res. 500W-1000VA max
Faston 14: NO aux1/light relay
Faston 6: C aux2/demist relay
250Vac 10A res. (2A) max
Faston 7: NO aux2/demist relay
Faston 10: C alarm relay
250Vac 10A res. (2A) max
Faston 11: NC alarm relay
Faston 12: NO alarm relay
2.1.3 NTC probe inputs
• measurement inputs for standard Carel NTC probes (10Kohm at 25 ˚C)
• compatibility with PLUG IN measurements, measuring range from
-50 to +90 ˚C
• 1mS input filter (fast transients, burst)
• connection with fixed screw terminals for wires from 0.5 to 1.5 mm
2
• distance max 30m for standards compliance (surge)
Terminal 24: NTC control probe (ambient) input signal (-50/+90˚C)
Terminal 25: NTC control probe reference signal
Terminal 26: NTC defrost probe input signal (-50/+90˚C)
Terminal 27: NTC defrost probe reference signal
Terminal 28: NTC product/defrost2 probe input signal (-50/+90˚C)
Terminal 29: NTC product/defrost2 probe reference signal
2.1.4 Digital inputs
• inputs from free contacts (not supplied) with closing current of 8-12mA
• 1mS filter input (fast transients, burst)
• connection with fixed screw terminals for wires from 0.5 to 1.5 mm
2
.
• distance max 30m for standards compliance (surge)
Terminal 31: digital input 1
Terminal 30: digital input 1 reference
Terminal 33: digital input 2
Terminal 32: digital input 2 reference
Note: The use of the inputs can be programmed by setting the corre-
sponding parameters (multi-function inputs)
2.1.5 Light presence sensor input
• input from photocell to signal the opening of the doors on
refrigerated display cabinets, one or two sensors featured
• connection with fixed screw terminals (2-way) for wire cross-sections
from 0.5 to 1.5 mm
2
.
• Maximum distance 30 metres for standards compatibility (surge).
Terminal 34: photocell reference (common)
Terminal 35: photocell input (light presence)
Note: One input only is available, with the possibility of connecting one
or two sensors in parallel