3. For μChiller Standard and Enhanced models (with On/Off compressor), select the "Refrigerants"
section and then the refrigerant charged on the unit.
4. (NOTE: the BLDC compressor configuration must be performed with the unit OFF and the "Crankcase
heater" function disabled (par. P034 = 0). For High Efficiency models (HE, with BLDC compressor), first
import the BLDC compressor configuration, selecting the "BLDC Compressors" section, and then set
the brand and model of compressor installed on the unit.
Configuration procedure
1. Connect to the BMS port on the μChiller controller, as shown in the figure;
2. Open Applica Desktop; a window will be opened with the right part of the top bar as shown below:
Fig.3.k
3. Select "Add target" and assign it a meaningful name (e.g. "µChiller");
4. In the "COM Port" field, enter the COM port used for the USB connection to the USB/RS485 converter;
5. Configure the connection parameters (Baudrate=115200, Bits=8, Parity=None, Stop Bits=Two, Serial
Node=1) as shown in the figure (the data are saved automatically);
Fig.3.l
6. Use "Connect" to connect to the μChiller (which must be powered on);
7. Once connected, select the "Configurations" label: the command bar will be displayed, as shown:
Fig.3.m
8. Select "File -> Import" to load the configurations downloaded from KSA;
9. Select the configuration to be applied to the μChiller, and then "Apply Configuration";
ENG
µC0300053EN rel. 1.0 – 23.07.2018