User
Code
Description
Def
Min
Max
UOM
S
C017
Max high pressure threshold (HP)
65.0
0.0
999.9
°C
S
S029
Source fan in heating: set point
10.0
0.0
99.9
°C
S
S035
Source fan: differential in heating
5.0
0.0
99.9
K
S
S036
Modulating source fan: min speed value
20.0
0.0
100.0
%
S
S037
Modulating source fan: max speed value
80.0
0.0
100.0
%
The control diagram is shown below:
Fig.5.r
Key
Max speed
Modulating source fan: max speed value
Min speed
Modulating source fan: min speed value
SP
Control set point
DT
Control differential
Tc max
Maximum condensing temp.
Te
Evaporation temperature
In the graph, some offsets are expressed with a numerical value, indicating that they are not modifiable
on the display but rather are fixed parameters. The current calculated set point value is displayed on the
dashboard.
5.13.4 "Low noise” function
This function reduces the noise emitted by modulating fans by increasing the set point at night.
User
Code
Description
Def
Min
Max
UOM
S
S020
Enable noise reduction
0/1=No/Yes
0
0
1
-
S
S021
Noise reduction time band: start hours
22
0
23
h
S
S022
Noise reduction time band: start minutes
30
0
59
min
S
S023
Noise reduction time band: end hours
8
0
23
h
S
S024
Noise reduction time band: end minutes
30
0
59
min
S
S025
Source fan: noise reduction set point
45.0
0.0
999.9
°C
5.13.5 Fan anti-blocking function
For systems intended to operate in cold climates, μChiller modulates fan speed so as to prevent the unit
from shutting down due to frost formation. The function is activated when the outdoor temperature falls
below a threshold, and, instead of turning off the fans, keeps then on at a minimum speed. If the outside
temperature is reached when the fans are off, these are activated at start-up speed for a certain time, and
then switch to the minimum speed.
User
Code
Description
Def
Min
Max
UOM
S
S016
Source fan: cold climate temperature threshold
-0.5
-999.9
999.9
°C
S
S017
Source fan: min cold climate speed
10.0
0.0
100.0
%
S
S018
Source fan: cold climate speed at start-up
50.0
0.0
100.0
%
S
S019
Source fan: cold climate speed at start-up time
5
0
300
s
ENG