User
Display
Code
Description
Def.
Min.
Max. UOM
R/W
Modbus
0/1=no/yes
S
U069
Free cooling: activation differential
3.0
0.0
99.9
K
R/W
HR08 (2R)
S
U070
Free cooling: hysteresis
1.5
0.0
99.9
K
R/W
HR08 (2R)
S
U071
Design free cooling delta T
8.0
0.0
99.9
K
R/W
HR08 (2R)
S
U072
Water free cooling: valve closing threshold
5.0
-999.9
999.9°C
°C
R/W
HR09 (2R)
S
U073
Water free cooling: valve closing differential
3.0
0.0
99.9
K
R/W
HR09 (2R)
M
U074
Free cooling type
0=Air
1=Remote coil
2=Water
0
0
2
-
R/W
HR095
S
U075
Frost protection type
0=Heater
1=Pump
2=Heater/Pump
2
0
2
-
R/W
HR096
M
U076
Number of user pumps
1
1
2
-
R/W
HR097
M
U077
Type of unit
0=CH
1=HP
2=CH/HP
0
0
2
-
R/W
HR098
Tab.6.a
6.2 Compressor
User
Display
Code
Description
Def.
Min
Max
UOM
R/W
Modbus
CMP= Compressor
S
C000
Comp. 1 circuit 1: maintenance hour threshold
99
0
999
h
R/W
HR153
S
C001
Comp. 1 circuit 1: reset hour counter
0
0
1
-
R/W
CS023
S
x
C002
Comp. 1 circuit 1: operating mode
0=AUTO
1=OFF
2=ON
0
0
2
-
R/W
HR154
S
C003
Comp. 2 circuit 1: maintenance hour threshold
(x100)
99
0
999
h
R/W
HR155
S
C004
Comp. 2 circuit 1: reset hour counter
0
0
1
-
R/W
CS024
S
x
C005
Comp. 2 circuit 1: operating mode
0=AUTO
1=OFF
2=ON
0
0
2
-
R/W
HR156
S
C006
Comp. 1 circuit 2: maintenance hour threshold
(x100)
99
0
999
h
R/W
HR157
S
C007
Comp. 2 circuit 1: reset hour counter
0
0
1
-
R/W
CS025
S
x
C008
Comp. 2 circuit 1: operating mode
0=AUTO
1=OFF
2=ON
0
0
2
-
R/W
HR158
S
C009
Comp. 2 circuit 2: maintenance hour threshold
(x100)
99
0
999
h
R/W
HR159
S
C010
Comp. 2 circuit 2: reset hour counter
0
0
1
-
R/W
CS026
S
x
C011
Comp. 2 circuit 2: operating mode
0=AUTO
1=OFF
2=ON
0
0
2
-
R/W
HR160
M
C012
Min compressor on time
180
30
999
s
R/W
HR161
M
C013
Min compressor off time
60
30
999
s
R/W
HR162