ENG
Index Size
Ref.
Type Min/Max R/W UoM Description
104
1
BOOL
R
Comp1Circ2_On - Compr.1 circ.1 status (0=OFF, 1=ON)
105
1
BOOL
R
Comp2Circ2_On - Compr.2 circ.2 status (0=OFF, 1=ON)
106
1
BOOL
R
RelayAlrm - Global alarm relay
107
1
BOOL
R
CoolHeat - Unit in heating mode (0=Cooling, 1=Heating)
108
1
BOOL
R
FC_Status - Free cooling valve status (0=OFF, 1=ON)
109
1
BOOL
R
Antifreeze heater status
110
1
BOOL
R
Unit scheduler status
120
1
BOOL
R
SrcFanCirc1_On - Source fan circ.1 status (0=OFF, 1=ON)
121
1
BOOL
R
Source pump 1 status (0=OFF, 1=ON)
122
1
BOOL
R
UsrPmp1_On - User pump 1 status
123
1
BOOL
R
Reverse cycle valve circuit 1 status
124
1
BOOL
R
Oil equalization valve circuit 1 status
125
1
BOOL
R
SrcFanCirc2_On - Source fan circ.2 status (0=OFF, 1=ON)
127
1
BOOL
R
UsrPmp2_On - User pump 2 status
128
1
BOOL
R
Reverse cycle valve circuit 2 status
129
1
BOOL
R
Oil equalization valve circuit 2 status
131
1
BOOL
R
Defrost running on circuit 1
132
1
BOOL
R
Defrost running on circuit 2
134
1
BOOL
R
Unit status
143
1
BOOL
R
Compr.1 circuit 1 forced on by oil migration management
144
1
BOOL
R
Compr.2 circuit 1 forced on by oil migration management
145
1
BOOL
R
Compr.1 circuit 2 forced on by oil migration management
146
1
BOOL
R
Compr.2 circuit 2 forced on by oil migration management
148
1
BOOL
R
UsrFlw_Absent - User pump flow absent (0=Flow OK, 1=Flow absent)
Tab.6.b
6.3 Holding
Register
Index Size
Ref.
Type
Min/Max R/W
UoM Description
2
1
U000
INT
0..999
R/W
h
U000 - User pump 1 maintenance hour threshold (x100
3
1
U002
INT
0..2
R/W
U002 - User pump 1 manual mode (0=AUTO, 1=OFF, 2=ON)
4
1
U003
INT
0..999
R/W
h
U003 - User pump 2 maintenance hour threshold (x100
5
1
U005
INT
0..2
R/W
U005 - User pump 2 manual mode (0=AUTO, 1=OFF, 2=ON)
7
2
U006
REAL
-99.9..999.9 R/W
°C/°F
U006 - Cool setpoint low limit
9
2
U007
REAL
-99.9..999.9 R/W
°C/°F
U007 - Cool setpoint high limit
11
2
U008
REAL
0..999.9
R/W
°C/°F
U008 - Heat setpoint low limit
13
2
U009
REAL
0..999.9
R/W
°C/°F
U009 - Heat setpoint high limit
15
2
U011
REAL
-99.9..999.9 R/W
°C/°F
U011 - Starting temp. point for cool setpoint compensation
17
2
U012
REAL
-99.9..99.9
R/W
°C/°F
U012 - Ending temp. point for cool setpoint compensation
19
2
U013
REAL
-99.9..99.9
R/W
K/R
U013 - Max compensation for cool setpoint
21
2
U014
REAL
-99.9..999.9 R/W
°C/°F
U014 - Starting temp. point for heat setpoint compensation
23
2
U015
REAL
-99.9..99.9
R/W
°C/°F
U015 - Ending temp. point for heat setpoint compensation
25
2
U016
REAL
-99.9..99.9
R/W
K/R
U016 - Max compensation for heat setpoint
27
1
U018
INT
0..23
R/W
h
U018 - Scheduler start hour time band
28
1
U019
INT
0..59
R/W
min
U019 - Scheduler start minute time band
29
1
U020
INT
0..23
R/W
h
U020 - Scheduler end hour time band
30
1
U021
INT
0..59
R/W
min
U021 - Scheduler end minute time band
31
2
U023
REAL U006..U007 R/W
°C/°F
U023 - 2nd cool setpoint
33
2
U024
REAL U008..U009 R/W
°C/°F
U024 - 2nd heat setpoint
35
1
U025
INT
0..2
R/W
U025 - Analog setpoint input type (0=0-5V, 1=0-10V, 2=4-20mA)
37
2
U026
REAL
-99.9..99.9
R/W
°C/°F
U026 - Remote setpoint min value
39
2
U027
REAL
-99.9..99.9
R/W
°C/°F
U027 - Remote setpoint max value
41
1
S023
INT
0..23
R/W
h
S023 - Low noise end hour time band
42
1
S024
INT
0..59
R/W
min
S024 - Low noise end minute time band
92
| 6. Supervisor table
µC0300053EN rel. 1.0 – 23.07.2018