6. Supervisor table
μChiller provides a database of supervisor variables via Modbus RTU protocol over RS485 (BMS port on
the μChiller controller).
The BMS port has the following default settings:
l
baud rate 115,200;
l
data bits 8;
l
no parity;
l
stop bits 1.
See "Parameter table: BMS port" to set different values.
"Index" is the address specified in the Modbus® frame.
6.1 Coil Status
Index Size
Ref.
Type Min/Max R/W UoM Description
0
1
U001
BOOL
R/W
U001 - User pump 1 reset hour counters
1
1
U004
BOOL
R/W
U004 - User pump 2 reset hour counters
2
1
U010
BOOL
R/W
U010 - Enable setpoint compensation (0=Disabled, 1=Enabled)
3
1
U017
BOOL
R/W
U017 - Enable scheduler (0=Disabled, 1=Enabled)
4
1
U022
BOOL
R/W
U022 - Type of scheduling (0=Switch OFF, 1=Change setpoint)
5
1
U034
BOOL
R/W
U034 - Changeover type cold/heat (0=Keyboard, 1=DIn)
6
1
U036
BOOL
R/W
U036 - Startup regulation probe (0=Return, 1=Delivery)
7
1
U038
BOOL
R/W
U038 - Run regulation probe (0=Return, 1=Delivery)
8
1
U057
BOOL
R/W
U057 - Remote alarm input logic (0=N.C., 1=N.O.)
9
1
U058
BOOL
R/W
U058 - Cool/Heat input logic (0=N.O., 1=N.C.)
10
1
U059
BOOL
R/W
U059 - Remote unit ON/OFF input logic (0=N.O., 1=N.C.)
11
1
U060
BOOL
R/W
U060 - User pump flow input logic (0=N.C., 1=N.O.)
12
1
U061
BOOL
R/W
U061 - User pump overload input logic (0=N.C., 1=N.O.)
13
1
U062
BOOL
R/W
U062 - 2nd setpoint input logic (0=N.O., 1=N.C.)
14
1
U063
BOOL
R/W
U063 - User pump output logic (0=N.O., 1=N.C.)
15
1
U064
BOOL
R/W
U064 - Global alarm relay output logic (0=N.C., 1=N.O.)
16
1
U065
BOOL
R/W
U065 - Free-Cooling valve output logic (0=N.O., 1=N.C.)
17
1
U066
BOOL
R/W
U066 - Antifreeze heater output logic (0=N.O., 1=N.C.)
18
1
U067
BOOL
R/W
U067 - Alarm relay configuration (0=Regulation alarms, 1=All alarms)
19
1
U068
BOOL
R/W
U068 - Enable Free-Cooling (0=Disabled, 1=Enabled)
20
1
E000
BOOL
R/W
E000 - ExV circ.1 enable manual mode
21
1
E002
BOOL
R/W
E002 - ExV circ.2 enable manual mode
22
1
Hd06 BOOL
R/W
Hd06 - Enable power request from BMS (0=Disabled, 1=Enabled)
23
1
C001
BOOL
R/W
C001 - Compr.1 circ.1 reset hour counters
24
1
C004
BOOL
R/W
C004 - Compr.2 circ.1 reset hour counters
25
1
C007
BOOL
R/W
C007 - Compr.1 circ.2 reset hour counters
26
1
C010
BOOL
R/W
C010 - Compr.2 circ.2 reset hour counters
27
1
C034
BOOL
R/W
C034 - High press. pressostat input logic (0=N.C., 1=N.O.)
28
1
C035
BOOL
R/W
C035 - Compr. overload input logic (0=N.C., 1=N.O.)
29
1
C036
BOOL
R/W
C036 - Compr. output logic (0=N.O., 1=N.C.)
30
1
C044
BOOL
R/W
C044 - Enable circuit destabilization (0=Disabled, 1=Enabled)
31
1
S001
BOOL
R/W
S001 - Source pump 1 reset hour counters
33
1
S009
BOOL
R/W
S009 - Source fan 1 circ.1 reset hour counters
34
1
S013
BOOL
R/W
S013 - Source fan 1 circ.2 reset hour counters
35
1
S020
BOOL
R/W
S020 - Enable low noise (0=Disabled, 1=Enabled)
37
1
S043
BOOL
R/W
S043 - Enable sliding defrost (0=Disabled, 1=Enabled)
38
1
S055
BOOL
R/W
S055 - Compr. behavior in post-defrost phase (0=Compr. is OFF, 1=Compr. is turned ON)
39
1
S061
BOOL
R/W
S061 - Source fan output logic (0=N.O., 1=N.C.)
ENG
µC0300053EN rel. 1.0 – 23.07.2018
6. Supervisor table |
89