Index Size
Ref.
Type
Min/Max R/W
UoM Description
43
2
U028
REAL
-99.9..99.9
R/W
K/R
U028 - Remote setpoint offset
48
1
E046
INT
1..24
R/W
E046 - ExV valve type for EVD EVO (1=CAREL EXV, ...)
49
2
U031
REAL
0..99.9
R/W
K/R
U031 - High water temp. setpoint offset
51
1
U032
INT
0..99
R/W
min
U032 - High water temp. startup delay
52
1
U033
INT
0..999
R/W
s
U033 - High water temp.run delay
53
1
U035
INT
0..999
R/W
min
U035 - Changeover delay time
54
1
U037
INT
0..999
R/W
s
U037 - Delay time between Startup PID and Run PID
55
2
U039
REAL
0..999.9
R/W
U039 - Startup PID Kp
57
1
U040
INT
0..999
R/W
s
U040 - Startup PID Ti
58
1
U041
INT
0..99
R/W
s
U041 - Startup PID Td
59
2
U042
REAL
0..999.9
R/W
U042 - Run PID Kp
61
1
U043
INT
0..999
R/W
s
U043 - Run PID Ti
62
1
U044
INT
0..99
R/W
s
U044 - Run PID Td
63
1
U045
INT
0..999
R/W
s
U045 - User pump flow alarm startup delay
64
1
U046
INT
0..99
R/W
s
U046 - User pump flow alarm run delay
65
1
U047
INT
0..999
R/W
s
U047 - Compr. delay ON since the user pump ON
66
1
U048
INT
0..999
R/W
s
U048 - User pump delay OFF since the compr. OFF
67
1
U049
INT
0..999
R/W
h
U049 - User pump rotation time
68
2
U050
REAL
-99.9..999.9 R/W
°C/°F
U050 - Antifreeze user alarm threshold
70
2
U051
REAL
0..999.9
R/W
K/R
U051 - Antifreeze user alarm differential
72
1
U052
INT
0..999
R/W
s
U052 - Antifreeze user alarm delay time at 1K below threshold
73
2
U053
REAL
-99.9..999.9 R/W
°C/°F
U053 - Antifreeze (with unit OFF) setpoint
75
2
U054
REAL
0..99.9
R/W
K/R
U054 - Antifreeze (with unit OFF) differential
78
1
DFr
INT
0..3
R/W
DFr - Force manual defrost (0= None, 1= Force defrost on circ. 1, 2= Force defrost on circ. 2, 3= Force
defrost on all circuits)
79
2
U055
REAL
-99.9..99.9
R/W
K/R
U055 - Probe offset of return water temp. from user
83
2
U056
REAL
-99.9..99.9
R/W
K/R
U056 - Probe offset of delivery water temp. to user
85
2
U069
REAL
0..99.9
R/W
K/R
U069 - Delta temp. to activate Free-Cooling
87
2
U070
REAL
0..99.9
R/W
K/R
U070 - Free-Cooling ON/OFF hysteresis
89
2
U071
REAL
0..99.9
R/W
K/R
U071 - Delta temp. Free-Cooling design (to reach unit nominal capacity)
91
2
U072
REAL
-99.9..999.9 R/W
°C/°F
U072 - Free-Cooling limit threshold (used to close FC valve: because FC gives water with temp. very
low)
93
2
U073
REAL
0..99.9
R/W
K/R
U073 - Free-Cooling limit differential
95
1
U074
INT
0..2
R/W
U074 - Free-Cooling type (0=Air, 1=Remote air coil, 2=Water)
96
1
U075
INT
0..2
R/W
U075 - Antifreeze type (0=Heater, 1=Pump, 2=Heater-Pump)
97
1
U076
INT
1..2
R/W
U076 - User pump number
98
1
U077
INT
0..2
R/W
U077 - Unit type (0=CH, 1=HP, 2=CH/HP)
99
1
E001
INT
0..65535
R/W
Steps E001 - ExV circ.1 manual mode steps
100
1
E003
INT
0..65535
R/W
Steps E003 - ExV circ.2 manual mode steps
101
2
E004
REAL
-40..180
R/W
K/R
E004 - ExV SH setpoint in cool
103
2
E005
REAL
0..800
R/W
E005 - ExV SH regulation Kp in cool
105
2
E006
REAL
0..1000
R/W
s
E006 - ExV SH regulation Ti in cool
107
2
E007
REAL
0..800
R/W
s
E007 - ExV SH regulation Td in cool
109
2
E008
REAL
-40..180
R/W
K/R
E008 - ExV SH setpoint in heat
111
2
E009
REAL
0..800
R/W
E009 - ExV SH regulation Kp in heat
113
2
E010
REAL
0..1000
R/W
s
E010 - ExV SH regulation Ti in heat
115
2
E011
REAL
0..800
R/W
s
E011 - ExV SH regulation Td in heat
117
2
E012
REAL
-40..180
R/W
K/R
E012 - ExV low SH threshold in cool
119
2
E013
REAL
0..800
R/W
s
E013 - ExV low SH Ti in cool
121
2
E014
REAL
-40..180
R/W
K/R
E014 - ExV low SH threshold in heat
123
2
E015
REAL
0..800
R/W
s
E015 - ExV low SH Ti in heat
125
2
E016
REAL
-60..200
R/W
°C/°F
E016 - ExV LOP regulation threshold in cool
127
2
E017
REAL
0..800
R/W
s
E017 - ExV LOP regulation Ti in cool
129
2
E018
REAL
-60..200
R/W
°C/°F
E018 - ExV LOP regulation threshold in heat
131
2
E019
REAL
0..800
R/W
s
E019 - EEV LOP regulation Ti in heat
133
2
E020
REAL
-60..200
R/W
°C/°F
E020 - ExV MOP regulation threshold in cool
ENG
µC0300053EN rel. 1.0 – 23.07.2018
6. Supervisor table |