P/N
Description
ACS00CB000020
Connection cable L=1.5 m
ACS00CB000010
Connection cable L=3 m
Tab.1.c
1.3.2 EVD Evolution/EVD Evolution twin valve driver
The Enhanced and High Efficiency models have the driver built-into the controller, able to drive unipolar
valves (up to Carel model E3V, with a cooling capacity less than 90-100kW); all versions can be connected
to the external EVD Evolution driver to drive bipolar valves (with a higher cooling capacity).
Fig.1.b
1.3.3 Temperature sensors
NTC sensors for measuring the temperatures in the user circuit, the outdoor air or source, and the
refrigeration circuit. NTC**HT sensors are recommended for discharge temperature measurement (with
BLDC compressors in heat pump mode).
Fig.1.c
P/N
Type
Range
NTC060HF01
10 kΩ ±1% @25°C, IP67
-50 to 90°C strap-on
NTC060HP00
10 kΩ ±1% @25°C, IP67
-50 to 50 °C (105°C in air)
NTC060HT00
50 kΩ ±1% @25°C, IP67
-30 to 100°C RH95% in air (150°C in a
dry environment)
Tab.1.d
Note:
see 040010025 (ITA- ENG) /+040010026 (FRE- GER) for guidelines on installing the
sensors on the unit.
1.3.4 Pressure sensors
These measure:
1. evaporation pressure in the circuit, used to control superheat, manage the evaporator frost protection
function and the operating limits;
2. condensing pressure in the circuit, to control the condensing stage and manage the operating limits.
ENG
µC0300053EN rel. 1.0 – 23.07.2018
1. Introduction |
9