Ref.
Description
E1/E2
Evaporator 1/2
V1_C1
Solenoid valve circuit 1
V1_C2
Solenoid valve circuit 2
V2_C1
Thermostatic expansion
valve circuit 1
V2_C2
Thermostatic expansion
valve circuit 2
Ref.
Description
F1/2
Filter-drier 1/2
FL
Flow switch
CP1/2
Compressor 1/2
PU1/2
User pump 1/2
L1/2
Liquid receiver 1/2
Ref.
Description
P
Pressure probe/pressure switch
T
Temperature probe/thermostat
AL
Alarm
AL1_C1/2
Remote alarm circuit 1/2
2_Set
2nd set point
Tab.2.d
Analogue inputs - Master circuit 1
Ref. Description
Type
Configuration
parameters
S1 Return temperature from user
NTC
--
S2 Delivery temperature to user
NTC
--
S3 Not present
-
Hc00
S4 Condensing pressure
0-5V
Hc01; Hc02;
C040; C041; C042
S5 Evaporation pressure
0-5V
Hc01; C037; C038;
C039
S6 Not present
-
Hc03; U025;
U026; U027
Analogue inputs - Slave circuit 1
Ref. Description
Type
Configuration
parameters
S1 Not present
-
--
S2 Not present
-
--
S3 Not present
-
Hc00
S4 Condensing pressure
0-5V
Hc01; Hc02;
C040; C041; C042
S5 Evaporation pressure
0-5V
Hc01; C037;
C038; C039
S6 Not present
-
Hc05; U025;
U026; U027
Note:
l
probes S1 and S2 are not configurable, for the other probes, see the parameter table;
l
the discharge temperature probe is automatically assigned type NTC-HT.
Digital inputs - Master circuit 1
Ref. Description
Configuration
parameters
ID1 User pump flow switch
U060
ID2 Compressor 1 overload
C035
ID3 High pressure switch
C034
ID4 Not present
Hc06; C035;
U059; U058;
U062; U057;
U061
ID5 Remote alarm
Hc07; C035;
U059; U058;
U062; U057;
U061
ID6 2nd set point
HC08; C035;
U059; U058;
U062; U057;
U061
ENG
µC0300053EN rel. 1.0 – 23.07.2018
2. Installation |