4. User interface
4.1
Introduction
μChiller uses the user terminal to display the alarms, the main variables and to set the unit set points
(User level) and manual functions (Service level). The terminal has a 7- segment LED display with two
rows: the top row is 3-digit plus sign and decimal point; the bottom row is 4-digit plus sign (this can also
display the hour format -hh:mm and date - MM:DD). There is a buzzer, 14 operating icons and 4 buttons
for scrolling and setting the parameters. The terminal has NFC (Near Field Communication) and
Bluetooth (depending on the model) connectivity for interaction with mobile devices (on which the Carel
“Applica” app has been installed, available on Google Play for the Android operating system).
Note:
access levels: U=User; S=Service; M=Manufacturer. See the parameter table.
The unit of measure on the display can be changed via parameter UoM, accessed at a Service level,
including in the direct access functions menu.
Code
Description
Def.
UoM
Min
Max
Lev.
UoM
Unit of measure
0=°C/barg
1=°F/psig
0
-
0
1
S
The information and parameters accessible from the terminal and from the Applica app depend on the
access level and the unit configuration parameters.
4.2
User terminal
Key
1
Keypad
2
Main field
3
Device status and operating mode icons
Fig.4.a
Note:
the user terminal only allows access to certain parameters at the User and Service levels: to
access all of the Service and Manufacturer parameters, use the Carel Applica app or the configuration
and commissioning tool.
4.2.1 Keypad
Button
Description
Function
UP
- When scrolling: go to the previous parameter
- In programming mode: increase the value
DOWN
- When scrolling: go to the next parameter
- In programming mode: decrease in value
- Main menu:
- pressed briefly: unit dashboard display
- pressed and held (3 s): access User parameters (set point, unit
on-off, ...)
Alarm
- Pressed briefly: display active alarms and mute buzzer
- Pressed and held (3 s): reset alarms.
PRG
- When scrolling: access parameter programming mode
- In programming mode:
- pressed briefly: confirm value
- pressed and held (3 s): return to the main menu
4.2.2 Icons
The icons indicate the device operating status and operating modes, as shown in the following table.
ENG
µC0300053EN rel. 1.0 – 23.07.2018
4. User interface |
41