ENG
User
Display
Code
Description
Def.
Min.
Max. UOM
R/W
Modbus
S
U034
Operating mode changeover
0=Keypad
1=Digital input
0
0
1
-
R/W
CS005
S
U035
Cooling/heating changeover: delay
15
0
999
min
R/W
HR053
S
U036
Control probe at start-up
0=Return
1=Delivery
0
0
1
-
R/W
CS006
S
U037
PID control delay at start-up/operation
180
0
999
s
R/W
HR054
S
U038
Control probe in operation
0=Return
1=Delivery
1
0
1
-
R/W
CS007
S
U039
PID at start-up: Kp
6.0
0.0
999.9
-
R/W
HR05 (2R)
S
U040
PID at start-up: Ti
0: integral action disabled
180
0
999
s
R/W
HR057
S
U041
PID at start-up: Td
0: derivative action disabled
0
0
99
s
R/W
HR058
S
U042
PID in operation: Kp
10.0
0.0
999.9
-
R/W
HR05 (2R)
S
U043
PID in operation: Ti
0: integral action disabled
120
0
999
s
R/W
HR061
S
U044
PID in operation: Td
0: derivative action disabled
3
0
99
s
R/W
HR062
S
U045
User pump flow alarm: delay at start-up
10
0
999
s
R/W
HR063
S
U046
User pump flow alarm: delay in operation
3
0
99
s
R/W
HR064
S
U047
Compressor activation delay after user pump
30
0
999
s
R/W
HR065
S
U048
User pump shutdown delay after compressor
180
0
999
s
R/W
HR066
S
U049
User pump rotation time
12
0
999
h
R/W
HR067
S
U050
User side frost protection: alarm threshold
-0.8
-99.9
999.9
°C
R/W
HR06 (2R)
S
U051
User side frost protection: differential
30.0
0.0
999.9
K
R/W
HR07 (2R)
S
U052
User-side frost protection: delay time at 1K
30
0
999
s
R/W
HR072
S
U053
Unit OFF: frost protection set point
4.0
-99.9
999.9
°C
R/W
HR07 (2R)
S
U054
Unit OFF: frost protection differential
2.0
0.0
99.9
K
R/W
HR07 (2R)
S
U055
User side return temp. probe: offset
0.0
-99.9
99.9
K
R/W
HR07 (2R)
S
U056
User side delivery temp. probe: offset
0.0
-99.9
99.9
K
R/W
HR08 (2R)
S
U057
Remote alarm: input logic
0/1=NC/NO
0
0
1
-
R/W
CS008
S
U058
Cooling/heating input: logic
0/1=NO/NC
1
0
1
-
R/W
CS009
S
x
U059
Remote ON/OFF: input logic
0/1=NO/NC
1
0
1
-
R/W
CS010
S
U060
User pump flow switch: input logic
0/1=NC/NO
0
0
1
-
R/W
CS011
S
U061
User pump overload protector: input logic
0/1=NC/NO
0
0
1
-
R/W
CS012
S
U062
2nd set point: input logic
0/1=NO/NC
1
0
1
-
R/W
CS013
M
U063
User pump: output logic
0/1=NC/NO
0
0
1
-
R/W
CS014
S
U064
Global alarm relay: output logic
0/1=NC/NO
0
0
1
-
R/W
CS015
S
U065
Free cooling valve: output logic
0/1=NO/NC
0
0
1
-
R/W
CS016
M
U066
Frost protection heater: output logic
0/1=NO/NC
0
0
1
-
R/W
CS017
S
U067
Alarm relay configuration
0/1=Control alarms/All
0
0
1
-
R/W
CS018
S
U068
Free cooling: enable
0
0
1
-
R/W
CS019
78
| 6. Parameter table
µC0300053EN rel. 1.0 – 23.07.2018