Index Size
Ref.
Type Min/Max R/W
UoM Description
46
2
SEtA
REAL
R
°C/°F
SEtA - Actual setpoint used by thermoregulation
48
2
SSH1
REAL
R
K/R
SSH1 - Suction Superheat of circ.1
50
1
Opn1
INT
R
%
Opn1 - EEV position of circ.1
51
2
SSH2
REAL
R
K/R
SSH2 - Suction Superheat of circ.2
53
1
Opn2
INT
R
%
Opn2 - EEV position of circ.2
54
2
rUSr
REAL
R
°C/°F
rUSr - Return water temp. from user
56
2
dUSr
REAL
R
°C/°F
dUSr - Delivery water temperature to user
65
2
REAL
R
%
Fan1Req - Inverter request source fan circ.1
67
2
REAL
R
%
Fan2Req - Inverter request source fan circ.2
71
1
INT
R
Unit status (0=OFF by remote DI, 1=OFF by keyboard, 2=OFF by scheduler, 3=OFF by BMS, 4=OFF by
changeover mode Ch/HP, 5=OFF by alarm, 6=Unit in defrosting, 7=Unit ON)
90
2
rSPt
REAL
R
°C/°F
rSPt - Remote set point (from analog input)
92
2
REAL
R
%
PwrReq - Power request
94
2
REAL
R
%
FC_PrwReq - Free-Cooling regulation ramp
96
2
REAL
R
°C/°F
SrcSetP_Circ1 - Source fan circ.1 set point
98
2
REAL
R
°C/°F
SrcSetP_Circ2 - Source fan circ.2 set point
100
2
rps
REAL
R
rps
Actual rotor speed coming from inverter
102
2
Mc
REAL
R
A
Mc - Current motor current [A]
104
2
MP
REAL
R
kW
MP - Current motor consumption [kW]
106
2
Drt
REAL
R
°C/°F
Drt - Current drive temperature[°C]
108
1
AIHs1
UINT
R
AIHs1 - Records the last alarm (the more recent)
109
1
AIHs2
UINT
R
AIHs2 - Records the last-but-1st alarm
110
1
AIHs3
UINT
R
AIHs3 - Records the last-but-2nd alarm
111
1
AIHs4
UINT
R
AIHs4 - Records the last-but-3rd alarm
Tab.6.d
ENG
µC0300053EN rel. 1.0 – 23.07.2018
6. Supervisor table |