ENG
Index Size
Ref.
Type Min/Max R/W UoM Description
40
1
S062
BOOL
R/W
S062 - Source pump output logic (0=N.O., 1=N.C.)
41
1
S063
BOOL
R/W
S063 - Reverse valve output logic (0=N.O., 1=N.C.)
42
1
S064
BOOL
R/W
S064 - Source flow type (0=Independent, 1=Common)
44
1
S065
BOOL
R/W
S065 - Source fan type (0=Inverter, 1=ON/OFF)
46
1
S068
BOOL
R/W
S068 - Unit type (0=Air/Water, 1=Water/Water)
47
1
UoM
BOOL
R/W
UoM - Unit of measure used in display 2-Row (0=°C/bar, 1=°F/PSI)
48
1
Hc02
BOOL
R/W
Hc02 - Analog channel 4 enabling (0=Disabled, 1=Enabled)
49
1
Hc12
BOOL
R/W
Hc12 - Digital output 6 config. (0=Antifreeze, 1=Source fan / Source pump)
50
1
Hc13
BOOL
R/W
Hc13 - Enable buzzer (0=Disabled, 1=Enabled)
52
1
Ha02
BOOL
R/W
Ha02 - Sets controller internal clock (0=No set, 1=Set)
53
1
Hd03 BOOL
R/W
Hd03 - Enable NFC (0=Disabled, 1=Enabled)
54
1
UnSt
BOOL
R/W
UnSt - Unit ON/OFF command by keyboard (0=OFF 1=ON)
55
1
ModE BOOL
R/W
ModE - Cool/Heat mode by Keyboard (0=Cool, 1=Heat)
56
1
RES
BOOL
R/W
RES - Reset active alarms by BMS net (0=NO, 1=Reset)
59
1
ClrH
BOOL
R/W
ClrH - Delete alarms log (0=No, 1=Yes)
63
1
Hd05 BOOL
R/W
Hd05 - Enable unit ON/OFF command by BMS net (0=Disabled, 1=Enabled)
64
1
BOOL
R/W
Unit ON/OFF command by BMS
66
1
P016
BOOL
R/W
P016 - Oil equalization solenoid valve circuit 1 output logic (0:On if close;1:On if open)
67
1
P017
BOOL
R/W
P017 - Enable oil equalization function
68
1
P018
BOOL
R/W
P018 - Enable oil recovery function (0=OFF, 1=ON)
69
1
P034
BOOL
R/W
P034 - Enable cranckcase heater (0=OFF, 1=ON)
Tab.6.a
6.2 Input Status
Index Size
Ref.
Type Min/Max R/W UoM Description
0
1
A01
BOOL
R
Unit - Error in the number of retain memory writings
1
1
A02
BOOL
R
Unit - Error in retain memory writings
2
1
A03
BOOL
R
Unit - Remote alarm by digital input
3
1
A04
BOOL
R
Unit - Alarm remote set point probe broken or disconnected
4
1
A05
BOOL
R
Unit - Alarm user return water temperature probe broken or disconnected
5
1
A06
BOOL
R
Unit - Alarm user delivery water temperature probe broken or disconnected
6
1
A07
BOOL
R
Unit - Alarm tank temperature probe broken or disconnected
7
1
A08
BOOL
R
Unit - User pump 1 overload
8
1
A09
BOOL
R
Unit - User pump 2 overload
9
1
A10
BOOL
R
Unit - Flow switch alarm, no flow present with user pump 1 active
10
1
A11
BOOL
R
Unit - Flow switch alarm, no flow present with user pump 2 active
11
1
A12
BOOL
R
Unit - User pumps group alarm
12
1
A13
BOOL
R
Unit - User 1 pump maintenance
13
1
A14
BOOL
R
Unit - User 2 pump maintenance
14
1
A15
BOOL
R
Unit - High chilled water temperature
15
1
A16
BOOL
R
Unit - Alarm source return water/air temperature probe broken or disconnected
16
1
A17
BOOL
R
Unit - Source 1 pump maintenance
17
1
A18
BOOL
R
Unit - Free-cooling anomaly
18
1
A19
BOOL
R
Circuit 1 - Alarm discharge pressure probe broken or disconnected
19
1
A20
BOOL
R
Circuit 1 - Alarm condensing temperature probe broken or disconnected
20
1
A21
BOOL
R
Circuit 1 - Alarm suction pressure probe broken or disconnected
21
1
A22
BOOL
R
Circuit 1 - Alarm evaporating temperature probe broken or disconnected
22
1
A23
BOOL
R
Circuit 1 - Alarm discharge temperature probe broken or disconnected
23
1
A24
BOOL
R
Circuit 1 - Alarm suction temperature probe broken or disconnected
24
1
A25
BOOL
R
Circuit 1 - High pressure alarm by pressure switch
25
1
A26
BOOL
R
Circuit 1 - High pressure alarm by transducer
26
1
A27
BOOL
R
Circuit 1 - Low pressure alarm by transducer
27
1
A28
BOOL
R
Circuit 1 - Alarm freeze evaporation temperature
29
1
A30
BOOL
R
Circuit 1 - Overload compressor 1
90
| 6. Supervisor table
µC0300053EN rel. 1.0 – 23.07.2018
Содержание MuChiller UCHBD00001130
Страница 2: ......
Страница 6: ......
Страница 106: ...ENG 106 Chiller 0300053EN rel 1 0 23 07 2018...
Страница 107: ...ENG Chiller 0300053EN rel 1 0 23 07 2018 107...