Carel HB200C0300CE0 Скачать руководство пользователя страница 27

27

ENG

Heos BOX R704

 +0300140EN - rel. 1.0 - 25.05.2022

5.  MAINTENANCE

5.1  Routine maintenance

HEOS BOX is a product that requires minimal maintenance. Always comply 
with the minimum clearances described in "DIMENSIONS AND WEIGHTS" 
so as to be able to carry out routine maintenance operations safely.

The only maintenance operations required by the user are the following:
Maintenance operations to be carried out monthly:
•  visually inspect the outside of the box. Make sure there are no water 

spills or dripping due to condensation;

Maintenance operations to be carried out every three months:
•  keep the area around the box clean and uncluttered, making sure 

there is sufficient air change and enough free space in front of the two 
ventilation grilles for air intake and exhaust on the electrical panel (pos.  
3 and 4) and the refrigerant circuit compartment (pos. );

•  remove any built-up dust or debris from the two air grilles that may 

affect the flow of air inside the box;

•  leakage of refrigerant and/or lubricant fluid (stains or drops on the 

piping, on the piping insulation or the structure);

•  water spills or dripping due to condensation;  
•  build-up of dust or debris inside the electrical panel and/or refrigerant 

circuit compartment;

•  traces of moisture dissolved in the refrigerant, by observing the colour 

of the liquid/moisture indicator (pos. 16) installed in the refrigerant 
circuit compartment;

•  clean and, if appropriate, replace the water filter installed in the water 

line outside of the unit.

Maintenance operations to be carried out every six months:
•  visually inspect the inside of the box every six months. It is forbidden 

to remove the outer protection panels without first disconnecting the 
unit from the power supply, moving disconnect switch QS1 to OFF (see 
the wiring diagram). Temporarily remove the protective panels on the 
refrigerant circuit compartment and the electrical panel, and make sure 
the following are absent:

5.2  One-off service and spare parts list

REFRIGERATION UNIT

References

Description

1

Compressor

15

Filter-drier 

21

Ball valve at refrigerant inlet 

18

Ball valve at refrigerant outlet 

6

Check valve 

14

Safety valve

7

Plate heat exchanger-condenser 

13

Liquid receiver 

2

Discharge temperature probe 

12

Liquid temperature probe 

9

Water inlet temperature probe 

8

Water outlet temperature probe 

24

Suction temperature probe 

23

Suction pressure transducer 

4

Discharge pressure transducer 

16

Liquid/moisture indicator 

Needle valve for pressure ports 

Tab. 5.a 

ELECTRICAL PANEL

References

Description

-

Rear door disconnect switch, 3P 80A 

44

Black lever for disconnect switch 

32

Heos HEC electronic board

31

PSD2 inverter 

-

IP67 cable for pressure probes 

64

DC Choke for 3 PH inverter 

-

Fuses 

60

Telephone connector L=0.8 m 

Showcase air intake probe 

Showcase air outlet probe 

Defrost probe 

Tab. 5.b 

Notice: 

if replacing the Carel PSD inverter, when restarting the unit, 

make sure that the Heos controller writes the “PEC” safety parameters to 
the inverter. 
To do this, when switching the unit on, the Heos controller must be:
•  set as OFF
•  with the driver STO contact open

For further details, see the control 0300145EN.

Содержание HB200C0300CE0

Страница 1: ...C o n t r o l S o l u t i o n s E n e r g y S a v i n g s NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT HEOS BOX R744 User manual Assembly instructions including user and maintenance inf...

Страница 2: ......

Страница 3: ...uit 12 2 11 Electrical panel 13 2 12 Requirements for positioning the unit and multi evaporator layout 14 3 HANDLING 19 3 1 Opening the packaging 19 3 2 Positioning the unit 19 4 INSTALLATION 21 4 1 M...

Страница 4: ......

Страница 5: ...EQUIPMENT HAZARD The unit is supplied sealed with an inert gas nitrogen pre charge of around 1 bar 14 5 psi above atmospheric pressure Take all necessary precautions to avoid material from being expe...

Страница 6: ...equivalent new equipment on a one to one basis or one to zero for equipment less than 25 cm on their longest side 3 the equipment may contain hazardous substances the improper use or incorrect dispos...

Страница 7: ...d with a Carel unipolar electronic expansion valve which is not supplied with the unit Appropriate sizing of the electronic valve where possible using Carel s selection tools allows Heosbox to be used...

Страница 8: ...configuration HBOPZGATY2000 Kit for supervisor WiFi connection HBOPZRAHY2000 Anti sweat heater management kit Tab 2 d 2 5 Connection diagrams local and su pervisor connection The Heosbox unit can be c...

Страница 9: ...y and therefore an external switch is needed for connection to the supervisory system Ethernet network Modbus Ethernet switch Fig 2 e On request a version of the controller with two Ethernet ports is...

Страница 10: ...edium temperature operation Evaporating temperature 10 C superheat 10 K subcooling 0 K condensing temperature 20 C compressor rotation speed 80 rps 4 Nominal conditions for low temperature operation E...

Страница 11: ...ulation of the current supplied by the electronic control does not include the optional anti sweat heater kit In fact the optional kit is not powered by the electronic controller but by the Heos Box m...

Страница 12: ...nser Water outlet connection Water inlet connection Suction pressure line Discharge Line Fig 2 h 2 26 30 29 1 14 15 8 12 13 25 22 6 17 16 23 24 4 9 10 11 27 19 18 7 20 28 21 5 3 Fig 2 i Ref Descriptio...

Страница 13: ...earth wire connection 43 Anti sweat heater kit 44 Electrical panel main switch 45 Electric panel ventilation air intake grille 46 Electrical panel power cable gland 47 Cable gland for digital output 6...

Страница 14: ...other acceptable configuration involves a common liquid line NB the last evaporator also needs to be well supplied with liquid and the suction lines in a multisplit arrangement Multiplex configuration...

Страница 15: ...ox Fig 2 p Heos Box lower than the evaporator P trap Reverse trap Suction line Heosbox Fig 2 q Possible oil top up Caution refer to section 4 6 2 12 3 Evaporator combination requirements When sizing t...

Страница 16: ...6 0 755 1 319 2 304 3 634 5 154 7 002 11 464 25 0 271 0 692 1 209 2 113 3 333 4 727 6 422 10 514 Tab 2 p MT application medium temperature Minimum cooling capacity in kW to ensure the oil is carried t...

Страница 17: ...ling capacity needed to carry the oil The tables below show the minimum cooling capacity as a function of Operating conditions Pipe diameter For the optimum diameter make sure that the required design...

Страница 18: ...420 5 395 7 652 10 396 17 020 20 0 409 1 043 1 821 3 181 5 019 7 117 9 670 15 831 25 0 375 0 956 1 670 2 917 4 602 6 526 8 867 14 516 Tab 2 w Minimum cooling capacity in kW to ensure the oil is carrie...

Страница 19: ...installed on the floor observing the clearances and making sure that there is natural ventilation to the unit Always avoid positioning installing the unit outdoors in a place where it is exposed to t...

Страница 20: ...ed for correct operation of the unit the following images show the distances from the surfaces to be allowed for during installation Side view Top view wall wall MIN 150 mm 5 91 in MIN 150 mm 5 91 in...

Страница 21: ...e using pipe couplings whose diameter and thickness varies according to the size of the unit see Refrigerant connections 4 1 Material supplied Heos Box is supplied complete with the following material...

Страница 22: ...ff placing disconnect switch QS1 and the switch or disconnect device on the HEOS BOX power supply line in the OFF position see the wiring diagram The mains power disconnect device must have a contact...

Страница 23: ...o the HEOS BOX power supply line in accordance with national regulations It is compulsory to follow the instructions on the wiring diagrams and comply with the minimum sizes of the multi core cables s...

Страница 24: ...gerant into the unit and are not technical specifications The expansion valves on the units must be correctly sized in order to complete the charging operation successfully CAREL Industries S p A may...

Страница 25: ...n 30 minutes 10 Disconnect the pump and close the discharge pressure port Fig 2 i 3 11 Carefully open the refrigerant inlet and outlet shut off valves Fig 2 i 18 and 21 4 8 2 Multi evaporator ME Cauti...

Страница 26: ...the Electrical Connections have been carried out as described in paragraph 4 4 4 Make sure that there is at least one display kit available see paragraph 2 3 If wanting to use the interface via smart...

Страница 27: ...outside of the unit Maintenance operations to be carried out every six months visually inspect the inside of the box every six months It is forbidden to remove the outer protection panels without firs...

Страница 28: ...l output 5 5 Free cable gland 1 17 Cable gland for digital output 6 6 Free cable gland 2 18 Heos electronic controller fuses 7 Free cable gland 3 19 Auxiliary terminals for optional anti sweat heater...

Страница 29: ...Now connect the wires downstream of the kit marked 08 and 09 to terminal J25 as shown on page QE EFS 7 of the panel s wiring diagram using a flat head screwdriver to help lever the spring When connect...

Страница 30: ...30 ENG Heos BOX R704 0300140EN rel 1 0 25 05 2022 Notes...

Страница 31: ......

Страница 32: ...BEL Caution Do not remove this copy of the unit label from the manual The customer is required to carefully keep all of the documentation supplied with the unit for any future maintenance or service U...

Отзывы: