27
ENG
Heos BOX R704
+0300140EN - rel. 1.0 - 25.05.2022
5. MAINTENANCE
5.1 Routine maintenance
HEOS BOX is a product that requires minimal maintenance. Always comply
with the minimum clearances described in "DIMENSIONS AND WEIGHTS"
so as to be able to carry out routine maintenance operations safely.
The only maintenance operations required by the user are the following:
Maintenance operations to be carried out monthly:
• visually inspect the outside of the box. Make sure there are no water
spills or dripping due to condensation;
Maintenance operations to be carried out every three months:
• keep the area around the box clean and uncluttered, making sure
there is sufficient air change and enough free space in front of the two
ventilation grilles for air intake and exhaust on the electrical panel (pos.
3 and 4) and the refrigerant circuit compartment (pos. );
• remove any built-up dust or debris from the two air grilles that may
affect the flow of air inside the box;
• leakage of refrigerant and/or lubricant fluid (stains or drops on the
piping, on the piping insulation or the structure);
• water spills or dripping due to condensation;
• build-up of dust or debris inside the electrical panel and/or refrigerant
circuit compartment;
• traces of moisture dissolved in the refrigerant, by observing the colour
of the liquid/moisture indicator (pos. 16) installed in the refrigerant
circuit compartment;
• clean and, if appropriate, replace the water filter installed in the water
line outside of the unit.
Maintenance operations to be carried out every six months:
• visually inspect the inside of the box every six months. It is forbidden
to remove the outer protection panels without first disconnecting the
unit from the power supply, moving disconnect switch QS1 to OFF (see
the wiring diagram). Temporarily remove the protective panels on the
refrigerant circuit compartment and the electrical panel, and make sure
the following are absent:
5.2 One-off service and spare parts list
REFRIGERATION UNIT
References
Description
1
Compressor
15
Filter-drier
21
Ball valve at refrigerant inlet
18
Ball valve at refrigerant outlet
6
Check valve
14
Safety valve
7
Plate heat exchanger-condenser
13
Liquid receiver
2
Discharge temperature probe
12
Liquid temperature probe
9
Water inlet temperature probe
8
Water outlet temperature probe
24
Suction temperature probe
23
Suction pressure transducer
4
Discharge pressure transducer
16
Liquid/moisture indicator
-
Needle valve for pressure ports
Tab. 5.a
ELECTRICAL PANEL
References
Description
-
Rear door disconnect switch, 3P 80A
44
Black lever for disconnect switch
32
Heos HEC electronic board
31
PSD2 inverter
-
IP67 cable for pressure probes
64
DC Choke for 3 PH inverter
-
Fuses
60
Telephone connector L=0.8 m
-
Showcase air intake probe
-
Showcase air outlet probe
-
Defrost probe
Tab. 5.b
Notice:
if replacing the Carel PSD inverter, when restarting the unit,
make sure that the Heos controller writes the “PEC” safety parameters to
the inverter.
To do this, when switching the unit on, the Heos controller must be:
• set as OFF
• with the driver STO contact open
For further details, see the control 0300145EN.