18
ENG
Heos BOX R704
+0300140EN - rel. 1.0 - 25.05.2022
MT application (medium temperature):
Minimum cooling capacity in kW to ensure the oil is carried in the
suction piping
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-10
10
5
0.494
1.262
2.204
3.850
6.074
8.614
11.704
19.160
10
0.468
1.193
2.085
3.642
5.745
8.147
11.069
18.121
15
0.439
1.121
1.958
3.420
5.395
7.652
10.396
17.020
20
0.409
1.043
1.821
3.181
5.019
7.117
9.670
15.831
25
0.375
0.956
1.670
2.917
4.602
6.526
8.867
14.516
Tab. 2.w
Minimum cooling capacity in kW to ensure the oil is carried in the
suction piping
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-5
10
5
0.527
1.345
2.350
4.106
6.477
9.186
12.480
20.431
10
0.499
1.272
2.222
3.882
6.124
8.685
11.800
19.318
15
0.468
1.194
2.087
3.645
5.750
8.155
11.080
18.138
20
0.435
1.111
1.940
3.389
5.346
7.582
10.302
16.865
25
0.399
1.018
1.778
3.106
4.899
6.948
9.441
15.455