Minimum cooling capacity in kW to ensure the oil is carried through an
evaporator with 1 circuit
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-25
10
5
0.179
0.457
0.798
1.393
2.198
3.117
4.235
6.933
10
0.169
0.432
0.754
1.318
2.079
2.949
4.006
6.558
15
0.159
0.406
0.709
1.238
1.953
2.770
3.763
6.161
20
0.148
0.377
0.659
1.152
1.817
2.577
3.501
5.732
25
0.136
0.346
0.605
1.056
1.666
2.363
3.211
5.257
Tab. 2.n
Minimum cooling capacity in kW to ensure the oil is carried through an
evaporator with 2 circuits
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-30
10
5
0.330
0.842
1.471
2.569
4.053
5.748
7.810
12.785
10
0.312
0.796
1.391
2.430
3.833
5.437
7.387
12.093
15
0.293
0.748
1.307
2.282
3.600
5.106
6.938
11.358
20
0.273
0.696
1.215
2.123
3.349
4.750
6.453
10.565
25
0.250
0.638
1.114
1.947
3.071
4.355
5.917
9.687
Tab. 2.o
Minimum cooling capacity in kW to ensure the oil is carried through an
evaporator with 2 circuits
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-25
10
5
0.358
0.913
1.595
2.787
4.396
6.234
8.470
13.867
10
0.339
0.864
1.509
2.636
4.158
5.897
8.012
13.117
15
0.318
0.811
1.417
2.476
3.906
5.540
7.527
12.322
20
0.296
0.755
1.319
2.304
3.634
5.154
7.002
11.464
25
0.271
0.692
1.209
2.113
3.333
4.727
6.422
10.514
Tab. 2.p
MT application (medium temperature):
Minimum cooling capacity in kW to ensure the oil is carried through an
evaporator with 1 circuit
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-10
10
5
0.297
0.757
1.322
2.310
3.644
5.168
7.022
11.496
10
0.281
0.716
1.251
2.185
3.447
4.888
6.642
10.873
15
0.264
0.672
1.175
2.052
3.237
4.591
6.238
10.212
20
0.245
0.626
1.093
1.909
3.011
4.270
5.802
9.499
25
0.225
0.574
1.002
1.750
2.761
3.916
5.320
8.709
Tab. 2.q
Minimum cooling capacity in kW to ensure the oil is carried through an
evaporator with 1 circuit
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-5
10
5
0.316
0.807
1.410
2.464
3.886
5.511
7.488
12.259
10
0.299
0.763
1.333
2.329
3.674
5.211
7.080
11.591
15
0.281
0.717
1.252
2.187
3.450
4.893
6.648
10.883
20
0.261
0.666
1.164
2.034
3.208
4.549
6.181
10.119
25
0.239
0.611
1.067
1.864
2.940
4.169
5.664
9.273
Tab. 2.r
Minimum cooling capacity in kW to ensure the oil is carried through an
evaporator with 2 circuits
T_evap
SH
T_cond
Piping nominal outside diameter (OD), mm
°C
K
°C
6
8
10
12
14
16
18
22
-10
10
5
0.593
1.514
2.645
4.621
7.289
10.337
14.044
22.992
10
0.561
1.432
2.502
4.370
6.894
9.777
13.283
21.746
15
0.527
1.345
2.350
4.104
6.475
9.182
12.476
20.424
20
0.490
1.251
2.185
3.818
6.022
8.541
11.604
18.997
25
0.450
1.147
2.004
3.500
5.522
7.831
10.640
17.419
Tab. 2.s