Heos BOX R704

 +0300140EN - rel. 1.0 - 25.05.2022

cause malfunctions. The water circuit must be thoroughly cleaned of 
any processing residues (shavings, dust, etc.) before being connected 
to the unit. The flow of water into the condenser must not contain any 
impurities that may obstruct the condenser and affect operation of the 
unit. It is recommended to install an inspectable “Y” filter at the inlet to 
each condenser to ensure adequate protection. It is recommended to 
use a filter with the same diameter as the piping (1”) and with a filtration 
capacity of at least 400 μm or finer. Regular maintenance must be 
performed on the inspectable filter so as to ensure correct operation of 
all the units connected to the water loop. The diameter of the water loop 
piping and the pressure head at the inlet to each individual HEOS BOX 
unit must be sized so as to ensure a water flow-rate at the condenser inlet 
in compliance with the nominal flow-rate stated in this document under 
“TECHNICAL SPECIFICATIONS”.
All the units have been designed to give a water-side pressure drop of 
between 20-25 kPa, so as to simplify installation in a loop with multiple 
units connected in parallel. By maintaining a pressure drop of 20-25 kPa 
between the condenser inlet and outlet on each unit, the water flow-
rate to the condenser is certain to be approximately equal to the value 
required for correct operation of the unit, as declared in the “TECHNICAL 
SPECIFICATIONS”.
The installer is responsible for the correct construction and balancing of 
the water circuit. Carel Industries S.p.A. declines all liability for water loop 
installations that do not comply with the aforementioned instructions and 
in such cases does not guarantee correct operation of the unit.

4.3  Feedwater specifications

The HEOS box units are designed to work with mains water mixed with 
ethylene glycol (antifreeze additive), with a concentration in proportion to 
the total volume of the water loop equal to:
•  Nominal*: 20%;
•  Maximum: 50%.

Notice: 

(*) reference percentage for unit performance shown in the 

“TECHNICAL SPECIFICATIONS”.
The antifreeze additive:
•  it is a necessary precaution if the water loop is served by a dry cooler 

and the outside temperature drops below 0°C.

•  It is mandatory for systems that use chillers to cool the water loop.
•  It is good practice to use antifreeze to prevent corrosion and ensure 

constant water circuit performance over time.

•  It is possible to use inhibited propylene glycol with a maximum 

concentration of 52% by volume. As propylene and ethylene glycol 
have different thermal properties, performance of the HEOS BOX unit 
may differ from the values shown in the “TECHNICAL SPECIFICATIONS”.

Caution:

  read the safety and technical data sheet for the antifreeze 

additive before handling the fluid and adding it to the water circuit.

4.4  Refrigerant connections

Refer to Figure 4.a.

Caution:

  before continuing, make sure the unit is powered off, 

placing disconnect switch QS1 and the switch or disconnect device on the 
HEOS BOX power supply line in the OFF position (see the wiring diagram).
The mains power disconnect device must have a contact opening 
distance that allows complete disconnection in overvoltage category III 
conditions; it must also be incorporated into the HEOS BOX power supply 
line in accordance with national regulations. The refrigerant connections 
supplied are stubs of bare copper pipes with variable diameter and 
thickness, depending on the size of the unit. It is good practice to use 
copper pipes of the same type and with the same diameter as those 
coming out of the unit, avoiding differences in diameter of more than one 
size.

CE versions

Model

From the evap-

orator (suction 

line)

To the evapo-

rator 

(liquid 

line)

Safety valve 

outlet 

(to be piped)

HB200C0300CE0 diam. 10 x 1 mm

diam. 8 x 1 mm

3/8” G (male)

HB200C0400CE0 diam. 10 x 1 mm

diam. 8 x 1 mm

3/8” G (male)

HB200C0600CE0 diam. 12 x 1 mm

diam. 8 x 1 mm

3/8” G (male)

HB200C1000CE0 diam. 12 x 1 mm

diam. 8 x 1 mm

3/8” G (male)

Tab. 4.b 

The unit must be connected to the evaporator section via refrigerant 
piping in a workmanlike manner, by qualified operators using braze 
welding. The piping must be securely fixed and not transmit vibrations to 
the HEOS BOX unit. 

Connection procedure

1.  Wear all personal protective equipment needed to complete the 

connection procedure: gloves, protective glasses and safety shoes.

2.  Make sure the unit is powered off, placing disconnect switch QS1 and 

the switch or disconnect device on the HEOS BOX power supply line 
in the OFF position (see the wiring diagram).

3.  Make sure that the unit is firmly anchored to the system it is part of, 

using all of the “L” brackets at the base of the structure.

4.  Open the refrigerant circuit cover panel.
5.  Check the pressure in the circuit, which should be about 1 bar.
6.  Expel the inert gas (nitrogen) from inside the unit. Use the pressure 

ports (pos. 3, 17 and 22) arranged on the suction side, on the 
compressor side and on the liquid line. Take care to avoid any danger 
of materials and/or fluids being expelled outside of the unit.

7.  Pipe the output of the safety valve to ensure safe discharge of the 

refrigerant fluid should the valve open.

8.  Remove the two plugs on the refrigerant inlet and outlet pipes.
9.  Cover the structure with a metal screen so as to not damage the paint.
10.  Cover the refrigerant shut-off valves with a wet rag (pos. 18 and 21) to 

avoid overheating that would damage them.

11.  Connect to the two refrigerant pipes, inlet (pos. 20) and outlet (position 

19) to the rest of the refrigerant circuit by braze welding.

12.  Open the two shut-off valves located near the refrigerant inlet and 

outlet pipes (pos. 18 and 21).

13.  After braze welding the refrigerant circuit, charge the circuit with 

nitrogen to a maximum pressure of 40 barg (580 psi) and check that 
there are no leaks by measuring the pressure with a pressure gauge or 
other suitable instruments.

The HEOS BOX unit cannot be connected to the evaporating system using 
any other type of connection from that specified, otherwise the warranty 
will be void.

Содержание HB200C0300CE0

Страница 1: ...C o n t r o l S o l u t i o n s E n e r g y S a v i n g s NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT HEOS BOX R744 User manual Assembly instructions including user and maintenance inf...

Страница 2: ......

Страница 3: ...uit 12 2 11 Electrical panel 13 2 12 Requirements for positioning the unit and multi evaporator layout 14 3 HANDLING 19 3 1 Opening the packaging 19 3 2 Positioning the unit 19 4 INSTALLATION 21 4 1 M...

Страница 4: ......

Страница 5: ...EQUIPMENT HAZARD The unit is supplied sealed with an inert gas nitrogen pre charge of around 1 bar 14 5 psi above atmospheric pressure Take all necessary precautions to avoid material from being expe...

Страница 6: ...equivalent new equipment on a one to one basis or one to zero for equipment less than 25 cm on their longest side 3 the equipment may contain hazardous substances the improper use or incorrect dispos...

Страница 7: ...d with a Carel unipolar electronic expansion valve which is not supplied with the unit Appropriate sizing of the electronic valve where possible using Carel s selection tools allows Heosbox to be used...

Страница 8: ...configuration HBOPZGATY2000 Kit for supervisor WiFi connection HBOPZRAHY2000 Anti sweat heater management kit Tab 2 d 2 5 Connection diagrams local and su pervisor connection The Heosbox unit can be c...

Страница 9: ...y and therefore an external switch is needed for connection to the supervisory system Ethernet network Modbus Ethernet switch Fig 2 e On request a version of the controller with two Ethernet ports is...

Страница 10: ...edium temperature operation Evaporating temperature 10 C superheat 10 K subcooling 0 K condensing temperature 20 C compressor rotation speed 80 rps 4 Nominal conditions for low temperature operation E...

Страница 11: ...ulation of the current supplied by the electronic control does not include the optional anti sweat heater kit In fact the optional kit is not powered by the electronic controller but by the Heos Box m...

Страница 12: ...nser Water outlet connection Water inlet connection Suction pressure line Discharge Line Fig 2 h 2 26 30 29 1 14 15 8 12 13 25 22 6 17 16 23 24 4 9 10 11 27 19 18 7 20 28 21 5 3 Fig 2 i Ref Descriptio...

Страница 13: ...earth wire connection 43 Anti sweat heater kit 44 Electrical panel main switch 45 Electric panel ventilation air intake grille 46 Electrical panel power cable gland 47 Cable gland for digital output 6...

Страница 14: ...other acceptable configuration involves a common liquid line NB the last evaporator also needs to be well supplied with liquid and the suction lines in a multisplit arrangement Multiplex configuration...

Страница 15: ...ox Fig 2 p Heos Box lower than the evaporator P trap Reverse trap Suction line Heosbox Fig 2 q Possible oil top up Caution refer to section 4 6 2 12 3 Evaporator combination requirements When sizing t...

Страница 16: ...6 0 755 1 319 2 304 3 634 5 154 7 002 11 464 25 0 271 0 692 1 209 2 113 3 333 4 727 6 422 10 514 Tab 2 p MT application medium temperature Minimum cooling capacity in kW to ensure the oil is carried t...

Страница 17: ...ling capacity needed to carry the oil The tables below show the minimum cooling capacity as a function of Operating conditions Pipe diameter For the optimum diameter make sure that the required design...

Страница 18: ...420 5 395 7 652 10 396 17 020 20 0 409 1 043 1 821 3 181 5 019 7 117 9 670 15 831 25 0 375 0 956 1 670 2 917 4 602 6 526 8 867 14 516 Tab 2 w Minimum cooling capacity in kW to ensure the oil is carrie...

Страница 19: ...installed on the floor observing the clearances and making sure that there is natural ventilation to the unit Always avoid positioning installing the unit outdoors in a place where it is exposed to t...

Страница 20: ...ed for correct operation of the unit the following images show the distances from the surfaces to be allowed for during installation Side view Top view wall wall MIN 150 mm 5 91 in MIN 150 mm 5 91 in...

Страница 21: ...e using pipe couplings whose diameter and thickness varies according to the size of the unit see Refrigerant connections 4 1 Material supplied Heos Box is supplied complete with the following material...

Страница 22: ...ff placing disconnect switch QS1 and the switch or disconnect device on the HEOS BOX power supply line in the OFF position see the wiring diagram The mains power disconnect device must have a contact...

Страница 23: ...o the HEOS BOX power supply line in accordance with national regulations It is compulsory to follow the instructions on the wiring diagrams and comply with the minimum sizes of the multi core cables s...

Страница 24: ...gerant into the unit and are not technical specifications The expansion valves on the units must be correctly sized in order to complete the charging operation successfully CAREL Industries S p A may...

Страница 25: ...n 30 minutes 10 Disconnect the pump and close the discharge pressure port Fig 2 i 3 11 Carefully open the refrigerant inlet and outlet shut off valves Fig 2 i 18 and 21 4 8 2 Multi evaporator ME Cauti...

Страница 26: ...the Electrical Connections have been carried out as described in paragraph 4 4 4 Make sure that there is at least one display kit available see paragraph 2 3 If wanting to use the interface via smart...

Страница 27: ...outside of the unit Maintenance operations to be carried out every six months visually inspect the inside of the box every six months It is forbidden to remove the outer protection panels without firs...

Страница 28: ...l output 5 5 Free cable gland 1 17 Cable gland for digital output 6 6 Free cable gland 2 18 Heos electronic controller fuses 7 Free cable gland 3 19 Auxiliary terminals for optional anti sweat heater...

Страница 29: ...Now connect the wires downstream of the kit marked 08 and 09 to terminal J25 as shown on page QE EFS 7 of the panel s wiring diagram using a flat head screwdriver to help lever the spring When connect...

Страница 30: ...30 ENG Heos BOX R704 0300140EN rel 1 0 25 05 2022 Notes...

Страница 31: ......

Страница 32: ...BEL Caution Do not remove this copy of the unit label from the manual The customer is required to carefully keep all of the documentation supplied with the unit for any future maintenance or service U...

Отзывы: