System 236E Installation Instructions
16
CL 17 and 18
Command Location 17: Status Events Reporting Codes - #1
0
0
0
0
(1) (2) (3) (4)
Default Values
1 7
Digit Position (1): Unit Status Report Code
0 = No
1 - F = Yes: this report code sent after each failure to communicate
Digit Position (4): Completed Programming Report Code
0 = No
1 - F = Yes: this report code sent on completion of panel programming
Digit Position (2): Watchdog Reset Report Code
0 = No
1 - F = Yes: this report code sent after each Watchdog reset
Digit Position (3): Failed To Communicate Report Code
This is a global command for CL 17 and CL 18.
If Position (1) is programmed with a "0", all Status Reports in CL 17 and CL 18 will be disabled.
If Position (1) is programmed with any value other than 0, all Status Reports in CL 17 and CL 18 which have
been enabled (not programmed with 0) will send reports. Status Reporting Codes will be a 2-digit code. The first
digit is the contents of CL 17 (1) and the second digit is the Report Code programmed for the specific event.
Command Location 18: Status Events Reporting Codes - #2
1 8
0
0
0
0
0
0
(1) (2) (3) (4) (5) (6)
Default Values
Digit Position (1): Bell Fuse Fail Report Code
0 = No
1 - F = Yes: this report code sent at Bell Fuse failure
Digit Position (2): Bell Fuse Restore Report Code
0 = No
1 - F = Yes: this report code sent at Bell Fuse restoral
Digit Position (3): AC Fail Report Code
0 = No
1 - F = Yes: this report code sent at AC failure
Digit Position (4): AC Restore Report Code
0 = No
1 - F = Yes: this report code sent at AC restoral
Digit Position (5): Low Battery Report Code
0 = No
1 - F = Yes: this report code sent at low battery voltage
Digit Position (6): Low Battery Restore Report Code
0 = No
1 - F = Yes: this report code sent when battery voltage returns to normal
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5