Switch Closure on P Terminal
Open Collector on P Terminal
6.6.3.2 C terminals
Switch-closure mode is a special case edge-count function that measures dry-contact switch-
closures or open collectors. The operating system filters bounces.
l
CRBasic instruction:
PulseCount()
See also
Pulse measurement specifications
6.6.4 Edge timing and edge counting
Edge time, period, and counts can be measured on P or C terminals. Feedback control using
pulse-width modulation (PWM) is an example of an edge timing application.
6.6.4.1 Single edge timing
A single edge or state transition can be measured on or C terminals. Measurements can be
expressed as a time (µs), frequency (Hz) or period (µs).
CRBasic instruction:
TimerInput()
6.6.4.2 Multiple edge counting
Time between edges, time from an edge on the previous terminal, and edges that span the scan
interval can be measured on or C terminals. Measurements can be expressed as a time (µs),
frequency (Hz) or period (µs).
l
CRBasic instruction:
TimerInput()
6.6.4.3 Timer input NAN conditions
NAN is the result of a
TimerInput()
measurement if one of the following occurs:
l
Measurement timer expires
l
The signal frequency is too fast
6. Measurements
75
Содержание CR1000X
Страница 1: ...Revision 02 21 2019 Copyright 2000 2019 Campbell Scientific ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 16: ...Appendix A Glossary 176 Appendix B Index 214 Table of Contents viii ...
Страница 20: ...l Smart sensors o SDI 12 o RS 232 o Modbus o DNP3 o TCP IP o RS 485 1 Data acquisition system components 4 ...
Страница 192: ......
Страница 237: ...wiring panel 5 Appendix B Index 220 ...