![Campbell CR1000X Скачать руководство пользователя страница 151](http://html1.mh-extra.com/html/campbell/cr1000x/cr1000x_product-manual_489087151.webp)
Keyword
Information and Location
RecNum
Record number increments only when the record is requested by support
software. Range = 0 to 2
32
.
l
Long data type
l
Read only
RevBoard
Electronics board revision in the form xxx.yyy, where xxx = hardware
revision number; yyy = clock chip software revision. Stored in flash
memory. Updated at startup.
l
String data type
l
Read only
RunSignature
Signature of the running binary (compiled) program. Value is
independent of comments or non-functional changes. Often changes
with operating-system changes. Updates after compiling and before
running the program.
l
Numeric data type
l
Read only
SerialNumber
CR1000X serial number assigned by the factory when the datalogger was
calibrated. Stored in flash memory. Updated at startup.
l
Numeric data type
l
Read only
SkippedScan
Number of skipped program scans (see
(p. 113) for
more information) that have occurred while running the CRBasic program.
Does not include scans intentionally skipped as may occur with the use of
ExitScan and Do / Loop instructions. Updated when they occur.
l
Numeric data type
SkippedSystemScan
Number of scans skipped in the background calibration. Enter 0 to reset.
See
,
, and
.
l
Numeric data type
StartTime
Time (date and time) the CRBasic program started. Updates at beginning
of program compile.
l
NSEC data type
l
Read only
9. Tips and troubleshooting
135
Содержание CR1000X
Страница 1: ...Revision 02 21 2019 Copyright 2000 2019 Campbell Scientific ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 16: ...Appendix A Glossary 176 Appendix B Index 214 Table of Contents viii ...
Страница 20: ...l Smart sensors o SDI 12 o RS 232 o Modbus o DNP3 o TCP IP o RS 485 1 Data acquisition system components 4 ...
Страница 192: ......
Страница 237: ...wiring panel 5 Appendix B Index 220 ...