l
If the open circuit is at the end of a very long cable, the test pulse may not charge the cable
(with its high capacitance) up to a voltage that generates NAN or a distinct error voltage.
The cable may even act as an aerial and inject noise which also might not read as an error
voltage.
l
The sensor may "object" to the test pulse being connected to its output, even for 100 µs.
There is little or no risk of damage, but the sensor output may be caused to temporarily
oscillate. Programming a longer settling time in the CRBasic measurement instruction to
allow oscillations to decay before the ADC may mitigate the problem.
6.1.3.4
Minimizing
power-related
artifacts
Some
Vac-to-Vdc
power
converters
produce
switching
noise
or
ac
ripple
as
an
artifact
of
the
ac-
to-dc
rectification
process.
Excessive
switching
noise
on
the
output
side
of
a
power
supply
can
increase
measurement
noise,
and
so
increase
measurement
error.
Noise
from
grid
or
mains
power
also
may
be
transmitted
through
the
transformer,
or
induced
electromagnetically
from
nearby
motors,
heaters,
or
power
lines.
High-quality
power
regulators
typically
reduce
noise
due
to
power
regulation.
Using
the
50
Hz
or
60
Hz
first
notch
frequency
(f
N1
)
option
for
CRBasic
analog
ue
input
measurement
instructions
often
improves
rejection
of
noise
sourced
from
power
mains.
The
CRBasic
standard
deviation
output
instruction,
StdDev()
,
can
be
used
to
evaluate
measurement
noise.
The
datalogger
includes
adjustable
digital
filtering,
which
serves
two
purposes:
l
Arrive as close as possible to the true input signal
l
Filter out measurement noise at specific frequencies, the most common being noise at 50
Hz or 60 Hz, which originate from mains-power lines.
Filtering time is inversely proportional to the frequency being filtered.
6. Measurements
51
Содержание CR1000X
Страница 1: ...Revision 02 21 2019 Copyright 2000 2019 Campbell Scientific ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 16: ...Appendix A Glossary 176 Appendix B Index 214 Table of Contents viii ...
Страница 20: ...l Smart sensors o SDI 12 o RS 232 o Modbus o DNP3 o TCP IP o RS 485 1 Data acquisition system components 4 ...
Страница 192: ......
Страница 237: ...wiring panel 5 Appendix B Index 220 ...