Float
or
Long
integer is converted to a
Boolean
, zero is False (0), any non-zero value will set
the Boolean to True (-1). The Boolean data type allows application software to display it as an
On/Off, True/False, Red/Blue, etc.
The CR1000X uses –1 rather than some other non-zero number because the
AND
and
OR
operators are the same for logical statements and binary bitwise comparisons. The number -1 is
expressed in binary with all bits equal to 1, the number 0 has all bits equal to 0. When –1 is anded
with any other number the result is the other number, ensuring that if the other number is non-
zero (true), the result will be non-zero
As String * size
specifies the variable as a string of ASCII characters, NULL terminated,
with an optional size specifying the maximum number of characters in the string. A string is
convenient in handling serial sensors, dial strings, text messages, etc. When size is not specified,
a default of 24 characters will be used (23 usable bytes and 1 terminating byte).
As a special case, a string can be declared
As String
* 1. This allows the efficient storage of a
single character. The string will take up 4 bytes in memory and when stored in a data table, but it
will hold only one character.
4.4.2 Data storage
Data can be stored in either IEEE4 or FP2 formats. The format is selected in the program
instruction that outputs the data, i.e. minimum, maximum, etc.
While
Float
(IEEE 4 byte floating point) is used for variables and internal calculations,
FP2
is
adequate for most stored data. Campbell Scientific 2 byte floating point (
FP2
)provides 3 or 4
significant digits of resolution, and requires half the memory space as
IEEE4
(2 bytes per value
vs 4).
Table 4-2: Resolution and range limits of FP2 data
Zero
Minimum magnitude Maximum Magnitude
0.000
±0.001
±7999.
The resolution of
FP2
is reduced to 3 significant digits when the first (left most) digit is 8 or
greater. Thus, it may be necessary to use
IEEE4
output or an offset to maintain the desired
resolution of a measurement. For example, if water level is to be measured and output to the
nearest 0.01 foot, the level must be less than 80 feet for
FP2
output to display the 0.01 foot
increment. If the water level is expected to range from 50 to 90 feet the data could either be
output in
IEEE4
or could be offset by 20 feet (transforming the range to 30 to 70 feet).
4. Data
32
Содержание CR1000X
Страница 1: ...Revision 02 21 2019 Copyright 2000 2019 Campbell Scientific ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 16: ...Appendix A Glossary 176 Appendix B Index 214 Table of Contents viii ...
Страница 20: ...l Smart sensors o SDI 12 o RS 232 o Modbus o DNP3 o TCP IP o RS 485 1 Data acquisition system components 4 ...
Страница 192: ......
Страница 237: ...wiring panel 5 Appendix B Index 220 ...