DATA LOGGER
WITH WWW SERVER
SM61 TYPE
USER’S MANUAL
QUICK START
1. ZESTAW REGULATORA
1. data logger SM61........................... 1 pc
2. quick start manual...........................1 pc
3. guarantee card............................... 1 pc
4. CD with the software and
user’s manual..................................1 pc
In the safety service scope, the meter meets to requirements of the
EN 61010-1 standard.
Observations concerning the operational safety:
· All operations concerning transport, installation and commissioning
as well as maintenance must be carried out by qualified, skilled per-
sonnel, and national regulations for the prevention of accidents must be
observed.
1. DATA LOGGER SET
2. OPERATIONAL SAFETY
3. DIMENSIONS AND FIXING WAY
Power and external inputs should be connect according to
the pic. 2 and table 1 in which is described destiny of the individual
terminals in SM61 data logger.
4. CONNECTION DIAGRAMS
Pic.1. Dimensions and fixing way
Termi-
nal
Description
1
Input line (positive terminal
input 1) or
line of alarm 1
2
Input line (negative terminal
input 1) or
line of alarm 1
3
Input line (positive terminal
input 2) or
line of alarm 2
4
Input line (negative terminal
input 2) or
line of alarm 2
5
GND line
6
Line B (RS-485)
7
Line A (RS-485)
8
Line 5 V d.c.
9
Line + supply
10
Line - supply
11
not used
12
Output TxD (RS-232)
13
Input RxD (RS-232)
14
Line GND
15
Line A (RS-485)
16
Line B (RS-485)
Pic.2. Electrical connections of
SM61 data logger.
The SM61 data logger is fixing on rail bracket 35 mm. Dimen-
sions and fixing way are shown at pic. 1.
7. ROZPOCZÊCIE PRACY
After right - click on the selected device from the list a new
menu shown in pic. 4.
Pic.4. This menu is shown after right-click.
Selecting option
Change IP
brings up a window allowing the
configuration of the following settings as in pic. 5.
IP address
Subnet mask
Gateway
on/off DHCP
Restart module after set
configuration
FTP server data port
FTP server command port
Web server port
Modbus TCP port
Pic.5. Change of settings IP
Table 1
Data logger SM61 has four communication interfaces::
1. PORT 1 - serial interface:
· purpose - communication with Master device,
· bus - RS-232, RS-485,
· terminals - 14, 15, 16 (RS-485) and 12, 13, 14 (RS-232),
· galvanically isolated from rest of the system,
· maximum length of bus depends on the speed of transmission
(for high speeds of up to severals tens of meters, for small,
eg. 9600 bit/s to about 1.2 km).
2. PORT 2 - serial interface:
· purpose - communication with Slave device,
· bus - RS-485,
· terminals - 5, 6, 7, 8,
· galvanically isolated from rest of the system,
· maximum length of bus depends on the speed of transmission
(for high speeds of up to severals tens of meters, for small,
eg. 9600 bit/s to about 1.2 km).
3. USB - serial interface:
· protocol of data exchange: Modbus RTU,
· purpose - device configuration,
· connection - mini USB.
4. LAN:
· protocol of data exchange: Modbus TCP,
· purpose - device configuration,
· allow to connect device to Ethernet network,
· connection - RJ-45.
The category of twisted pair according to European norm
EN 50171 minimal: class D (category 5) – for fast local network, includes
applications which uses the frequency band up to 100 MHz. Descrip-
tion of the connection is shown at table 2.
· EIA/TIA 568A for both connectors in simple connections SM61
to a hub or switch,
· EIA/TIA 568A for first connector and EIA/TIA 568B for second
connector in connection with crossover (connection SM61 to a computer).
After connection device to Ethernet network it is able to confi-
gure settings using HTTP protocol or Modbus TCP.
The data logger set include CD with USB driver and software
SM61Config, which is used to find devices in Ethernet network and con-
figure them by Modbus RTU (USB) or Modbus TCP (Ethernet) protocol.
5. DATA LOGGER CONFIGURATION
Notice:
To get full resistance of data logger on electromagnetic inter-
ference one should follow these rules:
· do not supply the data logger from the network which is near
pulse noise generators (inverters) and do not use common with
them grounding circuits,
· use network filters,
· all shields should be grounded or connected to the
protective unit, one sided the nearest to the data logger,
·
use the general rule, the wires leading different signals should be carried
out in the greatest distance from each other (no less then 30 cm),
the intersection of these beams is performed at 90
o
.
5.1. STARTING TO WORK
The device need to set basic information about IP protocol
at the first start (IP address, subnet mask, gateway). Needed information
should be given from local network administrator in which device will be
joined. Software SM61Config let the user configure settings using USB
protocol or using Ethernet network.
In the case of first configuration using Ethernet network please
open the SM61Config application and show the list of found data log-
gers by choosing
List of SM61 devices
from the left menu as it’s shown
in pic. 3.
After making changes please left - click on
OK
to close a win-
dow and save changes to the device.
Configuration can be done also by USB. To connect with
the device by UBS, please select from the software menu
Options
and choose type of communication as it’s shown at pic. 6.
Pic.6. Selection of the type of communication.
Then please go to the configuration by selection the option from left
menu (see fig. 3). Selecting the option allow change the configuration.
After changing the configuration one should save it and restart the devi-
ce to set the new configuration.
Language is changing by selection
Option -> Language
and
then selection language from available positions. After that close the
application and open again.
Notice:
After changing the parameters the device should be reset.
Pic.3. Left menu of SM61Config
Shown the list of found modules
Configuration of Ethernet settings
Configuration of serial port settings
Note:
The full version of the user’s manual is inserted in the
www.lumel.com.pl/en/ web site.
· Before switching the data logger on, one must check the correctness
of connections of the network.
· Before the remove of the casing one should switch off data logger
power and measurement circuits.
· The device is destined to be installed and used in industrial electro
magnetic environment conditions.
· A switch or a circuit - breaker should be located near the device, easy
accessible by the operator and suitable marked.
Symbols placed in the manual means:
Especially important, you should know before you connect
the data logger. Failure to follow the remarks could lead to
damage of the data logger.
Notice:
The removal of the data logger casing during the guarantee
contract period lead to its cancellation.
Port 1
Port 2
LAN
Supply dependent on
code version
(85...230...253 V a.c./d.c.
or 20...24...50 V a.c./d.c.)
INPUT
or
Supply depend on the
code version