Connection, installation / mounting
Product manual 2CKA001473B5342
│
35
6.5 Mounting
/
dismantling
6.5.1 Installation
sites
Fig. 6: Installation sites
■
When selecting the installation location, ensure that there is a distance to sources of heat or
cold.
■
Heat or cold sources influence the function of the internal temperature sensor.
■
The device should be mounted on a wall opposite the heat source. The distance to side
walls or door frames should be at least 50 cm. The distance to the floor should be about 150
cm.
■
Do not mount the device on an exterior wall. Low outside temperatures have an effect on
the temperature regulation.
■
The device must not come into direct contact with liquids.
■
Do not mount the device in direct sunlight, near radiators, windows, light sources or behind
curtains.
Mounting height
Fig. 7:
Mounting height
■
The mounting height is 1.50 m.