KNX communication objects
Application "Internal RTC"
Product manual 2CKA001473B5342
│
295
(0 - 100%)
Slat position
Input/
Output
1 byte
[5.001]
Percent
(0 - 100%)
K
-
S
U
A
Position status
Input
1 bit
[1.002]
Boolean
K
-
S
-
A
Upper end position status
Input
1 bit
[1.002]
Boolean
K
-
S
-
A
Bottom end position status
Input
1 bit
[1.002]
Boolean
K
-
S
-
A
Height status [0 - 100%]
Input
1 byte
[5.001]
Percent
(0 - 100%)
K
-
S
-
A
Slat status [0-100%]
Input
1 byte
[5.001]
Percent
(0 - 100%)
K
-
S
-
A
Height status [0 - 255]
Input
1 byte
[5.010]
Counting
pulses
(0 - 255)
K
-
S
-
A
Slat status [0-255]
Input
1 byte
[5.010]
Counting
pulses
(0 - 255)
K
-
S
-
A
Name
Object
function
Length
Data type
Flags
K
L
S
U
A
Block
Input
1 bit
[1.002]
Boolean
K
-
S
-
A
RTC control element
Control On/Off (slave)
Input
1 bit
[1.001]
Switching
K
-
S
U
A
External actual temperature
Input
2 bytes
[9.001]
Temperature
(°C)
K
-
S
U
A
Fault, actual temperature
(slave)
Input/
Output
1 bit
[1.001]
Switching
K
-
S
-
A
Operating mode
(slave)
Output
1 byte
[20.102]
HVAC mode
K
-
S
U
A
Override operating mode
(Master/Slave)
Input/
Output
1 byte
[20.102]
HVAC mode
K
-
S
U
A
Window contact
(master/slave)
Input/
Output
1 bit
[1.001]
Switching
K
-
S
U
A
Presence detector
(master/slave)
Input/
Output
1 bit
[1.001]
Switching
K
-
S
U
A
Fan coil manual confirmation
(Slave)
Input/
Output
1 bit
[1.011]
Status
K
-
S
U
A
Fan coil manual (heating)
confirmation (Slave)
Input/
Output
1 bit
[1.011]
Status
K
-
S
U
A
Fan coil manual (cooling)
confirmation (Slave)
Input/
Output
1 bit
[1.011]
Status
K
-
S
U
A
Содержание Busch-SmartTouch ST/A10.11-811