KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
259
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling" or "Cooling with additional stage" and parameter "Setpoint heating
comfort = setpoint cooling comfort" is set on "deactivated".
10.24.83 Setpoint settings — Increase for cooling standby by
Options:
Setting option between 0 - 15
Specifies the temperature in cooling mode when nobody is present. On devices with a display,
this mode is indicated by the standby icon.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages" and parameter "Setpoint for standby and Eco are
absolute values" is set on "deactivated".
10.24.84 Setpoint settings — Setpoint for cooling economy
Options:
Setting option between 10 - 40
Specifies the comfort temperature for cooling economy.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling" or "Cooling with additional stage" and parameter "Setpoint heating
comfort = setpoint cooling comfort" is set on "deactivated".
10.24.85 Setpoint settings — Increase for cooling economy
Options:
Setting option between 0 - 15
Specifies the temperature in cooling mode when nobody is present. On devices with a display,
this mode is indicated by the Eco icon.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages" and parameter "Setpoint for standby and Eco are
absolute values" is set on "deactivated".
10.24.86 Setpoint settings — Setpoint for cooling building protection
Options:
Setting option between 27 - 45
Function for protecting the building against heat. On devices with a display, this mode is
indicated by the heat protection icon. Manual operation is blocked.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling," "Cooling with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".